Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T10CM01503
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/30/2011 | REINFORCED MASONRY PRE-GROUT | Approved | ||
09/07/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) SITE WALL AT MAIN ENTRY AT 48" OK TO GROUT |
|
09/01/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* TRASH ENCLOSURE; NORTH RETAINING WALLS OK TO GROUT AND CAP: PROGRESS AREAS ARE TOPPED OUT |
|
04/26/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
04/25/2011 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
03/24/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) CMU WALLS: GL D.75/13.5-14 AT 22'; GL: A.25/AC-AD AT 14' OK TO GROUT PRGORESS AREAS |
|
03/22/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) MECH AND ELECT ROOMS (SOUTH) AT 16'; HALLWAY #123 EAST WALL AT 10' 8"; SOUTH EAST AT 16' OK TO GROUT |
|
03/14/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) EAST WALL #103, #101 EAST WALL AT 26' 4"-20' 8" ENTRY VESTIBLE AT 24' 4" |
|
03/10/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) NORTH EAST AND NORTH WALL #103 AT 20' 4"; ENTRY VESTIBLE AT 20' 4"; SOUTH WALL #101 AT 20' 4"; CLASSROOM #202 EAST WALL ( MID PORTION ) AT 16' 8" OK TO GROUT PROGRESS AREAS |
|
03/08/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) CMU WALLS AT 16' 8"-HALLWAY #124, EAST CLASSROOM (EXISTING) WALL; WEST WALL CLASSROOM #201 16'-24' OK TO GROUT |
|
03/04/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) CMU WALLS AT 9' 4" CLASSROOM #604 S. WALL; EAST WALL, NORTH WALL, CMU WALL AT 18' #201, 203, 202 SOUTH WALL, #202 EAST WALL-OK TO GROUT PROGRESS AREAS |
|
03/02/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) 4' LIFT ? 123 WEST WALL 201 TOP OUT SOUTH WALL 201 & 202, EAST WALL/202 |
|
02/28/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) CMU WALL WEST WALL AT ROOM #201 AT 4'-8' OK TO GROUT PROGRESS 2) CMU WALLS HALLWAY #123 AT ENTRY #123B WALLS TOPPED OUT AT 16' 4"; CLASSROOM #201 SOUTH WALL, CLASSROOM #202 SOUTH WALL AT 9' 4" OK TO GROUT |
|
02/25/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) CMU WALL IN HALLWAY #123 WEST AT DOOR #128 B-8' OK TO GROUT |
|
02/24/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) ENTRY VESTIBULE AT 12'-8"; GL: 11-14; CLASSROOM #202 TO GL: B AT 24''; EAST WALL OF #206 AT 20' BLDG #200-PERIMETER WALLS AT 4'-8" OK TO GROUT PROGRESS AREA |
|
02/22/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
02/16/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL 16' LIFT 6/6.A; 8-13/A 11/A-B, 20' LIFT 10/B-?; 12-8.5/F |
|
02/10/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG 3100: ROOM 111 (N.W. CORNER) AT 16'; #112B AT 16', #116 N. & N.W. WALLS AT 12', 115, 114, 117 AT 12' WEST WALLS OK TO GROUT PROGRESS AREAS |
|
02/08/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* SOUTH WALL OF BUILDING NUM 500 TOPPED OUT AT 18' OKAY TO GROUT |
|
02/07/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
02/01/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* GL 14/D TO SOUTH, C/13-14.13/BC, 11-8/6. ALL 12' LIFT 1ST LIFT9-8/A 8-6/A-F |
|
01/26/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG 100 AND 200 8' NOT INCLUDING LINTELS |
|
01/24/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) CMU WALLS AT 4' AFFE ROOMS #120, 121,122,206,207 AND 205 OK TO GROUT PROGRESS AREAS |
|
01/21/2011 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* 1) CONTRACTOR CANCELLED |
|
01/20/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) GL 15-17/L-J TOP OUT; 10.5/G-J 8' LIFT; 1ST LIFT BLDG 100 EAST WALL |
|
01/18/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG #300 NORTH WALL AT 24'; E & W WALLS RAKED AT 24'-18'; SOUTH WALL AT 18'; ROOM 306-307 AT 16'; BLDG #400 ROOMS 406-407 AT 16'; NORTH WALL AT 24'; EAST AND WEST GROUT PROGRESS AREAS |
|
01/11/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG #300 NORTH WALL ABOVE LINTELS AT 21'-4"; GL: D.5/5.5-11 20'-4"; BLDG #400 PERIMETER WALL AT 18'-4" EAST AND WEST WALLS RAKED AT 24'-18' OK TO GROUT PROGRESS AREAS |
|
01/10/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG #300-NORTH WALL TO 20' NOT LINTELS DOCUMENT CHANGE ML2 TO ML4 2) LINE 7-G + 0 J.2 TOP OUT, LINE J.2 7 TO 10 TOP OUT AND LINE 10-J TO G 1ST LIFT |
|
01/07/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG #300 LINTEL AT GL: D.5/8-9 AT 13'; BLDG #400 LINTEL GL: E/13-14 AT 13'; BLDG #100 STEM WALL GL: FOOTING BY EXISTING ENTRANCE; GL 6-11; 11/A-B OK TO GROUT PROGRESS AREAS |
|
01/05/2011 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG #300: GL E.5/9-11 AT 16' 2) BLDG #400: PERIMETER CMU WALLS (EXCEPT ENTRY AREA E/13-14) ALL AT 16' 3) BLDG #500, GL: AB/A1-A5 AT24'; A1/AB-AC AT RAKER WALL 16'-24'; A5/AB-AC RAKED AT 16'-24'; AC/A1-A5 AT 16' OK TO GROUT PROGRESS AREAS |
|
12/29/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG #300-NORTH WALL AT 8'-12'; GL D.75/6-8; D7.5/9-10.75 OK TO GROUT PORGRESS AREAS |
|
12/27/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) 12' LIFT ON 300 EAST, SOUTH & WEST; 12' LIFT AT 400, 16' LIFT ON 500 WEST, NORTH & EAST |
|
12/22/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
12/21/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG #500 GL: A1-AB-AC; AC/A1-A5; A5/AB-AC AT 12' OK TO GROUT PROGRESS AREAS |
|
12/20/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 2ND LIFT BULDING 300 |
|
12/16/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) EXTERIOR WALLS CLASSROOM #301 AT 0"-48" OK TO GROUT PROGRESS AREAS |
|
12/13/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) 1ST LIFT ROOM 508 |
|
12/10/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) ROOM 601 SOUTH AND EAST WALL OK TO ADD EXTRA BLK AT M1 LINTEL TO ACHEIVE 16' 2ND LIFT |
|
12/08/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG 601 TOP OUT, BLDG 600 1ST LIFT, BLDG 500 3RD LIFT NEEDS SPECIAL INSPECTION 2) PROVIDE RFI ML1 LINTELS THAT ARE NOT 16" THICK |
|
12/05/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG 500 2ND LIFT OK |
|
12/01/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
11/30/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG #400 INTERIOR AND EXTERIOR WALLS AT 4'-8' OK TO GROUT PROGRESS AREAS |
|
11/23/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG #400-INTERIOR AND EXTERIOR WALLS AT 48" OK TO GROUT; WING WALL FROM #400 TO #500 |
|
11/15/2010 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO INSPECTION ON 2ND LIFT, NO ACCESS FOR 3RD LIFT |
|
11/10/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BLDG 600-PREP ROOM-1ST LIFT AT 4'-8' OK TO GROUT PROGRESS AREAS |
|
11/05/2010 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* |