Permit: T07CM03275
Permit Details
Apply Date:
08/06/2007
Applicant:
N/A
Description:
TI:RETAIL
Contractors:
- BURKDELLE CONTRACTORS L L C
Permit Reviews
Permit Number - T07CM03275
Permit Status: C of o
Permit Description: TI:RETAIL
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
08/06/2007 | PLANS OK TO SUBMIT - 3RD PARTY | 08/06/2007 | COMPLETED |
08/06/2007 | 3RD PARTY REVIEW-COMMERCIAL TI | 09/12/2007 | COMPLETED |
09/12/2007 | POST 3RD PARTY REVIEW | 09/14/2007 | COMPLETED |
09/17/2007 | POST 3RD PARTY REVIEW | 09/17/2007 | COMPLETED |
12/31/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 12/31/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07CM03275
Permit Status: C of o
Permit Description: TI:RETAIL
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/06/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T07CM03275
Permit Description: TI:RETAIL
Total Completed Inspections - 31
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/26/2007 | BUILDING PRE-SLAB | GDABBS | Approved | IVRS - Inspection :* SLAB INFILL FROM EXISTING BRICK WALLS TO THE SOUTH EXTENT OF NEW BLDG. PAD |
10/10/2007 | EXCAVATION/LAYOUT REBAR & ZON | AQUIROZ | Approved | IVRS - Inspection :* |
10/15/2007 | REINFORCED MASONRY PRE-GROUT | AQUIROZ | Approved | IVRS - Inspection :* |
10/24/2007 | EXT METAL CLIPS/EXT SHEATHING | JBURGE | Approved | IVRS - Inspection :* FIRE SHEETROCK (2 LAYERS) - 4 @ PARAPETS NORTH, EAST, SOUTH WALL (4' WRAP) - EAST & WEST - OK TO TAPE PROGRESS AREAS |
10/26/2007 | ROOF NAILING | GDABBS | Approved | IVRS - Inspection : See detailed listing on site.| 999* NO ROOF TRUSS APPROVED SUBMITTALS ON SITE NAILING @ ROOF SHEATHING OK TO PROCEED |
11/05/2007 | MECHANICAL - ABOVE CEILING | MRAMBER | Approved | IVRS - Inspection :* - CONDENSATE PIPING TO BE INCREASED TO 1" WHERE TWO UNITS ARE "TEE" TOGETHER - GP-1 PROVIDE DUCT SUPPORT ON 14" DUCT SO THAT FLEX CONNECTOR IS NOT USED FOR SUPPORT - GP-2 PROVIDE DUCT SUPPORT ON BOTH 10" DUCT SO FLEX CONNECTOR IS NOT USED FOR SUPPORT |
11/05/2007 | FRAMING | JBURGE | Approved | IVRS - Inspection :* OK TO SHEETROCK ONE SIDE; BOTH PENDING ELECTRIC & PLUMBING INTERMEDIATES |
11/14/2007 | ELECTRIC - INTERMEDIATE | CCLEMENS | Approved | IVRS - Inspection :* OK WALL COVER NO SERVICE/PANEL INSPECTION AT THIS TIME |
11/28/2007 | PLUMBING - ROOF DRAINS | RMYERS | Approved | IVRS - Inspection :* 1. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THREAD OF BRANCHES: THEN NO MORE THAN FOUR FEET BETWEEN HANGERS 2. NOT INSTALLED PER PLAN ROOF DRAIN LOCATIONS AS REFERENCED ON A.1.3 ARE NOT ON THE PLUMBING PLAN - CHANGES TO THE PLAN MUST BE AUTHORIZED BY THE ENGINEER. 3. LAVATORY CARRIERS COVERED W/O INSPECTION SEE NOTE ABOVE (11/13/07) |
11/29/2007 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection :* |
12/04/2007 | FIRE - FINAL | CSCHULTZ | Approved | |
12/10/2007 | ELECTRIC - CABLE DROP | CCLEMENS | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO POST BOND WITH CITY OF TUCSON FOR POWER 2. BOND NIPPLE BETWEEN METER BASE & DISCONNECT (LUG LOOSE) 3. IDENTIFY "SERVICE DISCONNECT" AS SUCH 4. INSTALL FUSES 5. SECURE G.E.C TO STRUCTURE 6. IDENTIFY PHASE CONDUCTORS 7. TIGHTEN ALL CONNECTIONS 8. BOND WATER & GAS PIPES 9. FINISH ALL TRIM/NO OPEN WIRING 10. INSTALL PROPER LENGTH NIPPLE BETWEEN DISCONNECT AND PANEL. LOCKNUTS ARE REQUIRED BOTH SIDES ENTERING ENCLOSURES (2 INTO DISCONNECT, 2 INTO PANEL) 11. CLEAN OUT INSIDE OF PANEL DO NOT CALL BEFORE ALL HAS BEEN COMPLETED |
12/10/2007 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* ALL CHANGES TO THE PLAN, MUST BE ACCOMPANIED BY REDLINES. REDLINES ARE TO BE COMPLETED AT TIME OF INSPECTION. SUPPORT RPPBP TO WALL. |
12/14/2007 | ELECTRIC - TEMP POWER FOR TEST | CCLEMENS | Approved | IVRS - Inspection :* |
12/14/2007 | TEP CLEARANCE - PM | BFLORES | Approved | TEC PER C.CLEMENS |
01/03/2008 | ENGINEERING - FINAL | MRUSSO | Approved | |
01/03/2008 | NPPO - FINAL | ACONNOR | Approved | N/A |
01/03/2008 | LANDSCAPE - FINAL | ACONNOR | Approved | N/A |
01/03/2008 | SIGN - FINAL | JYBARRA | Approved | |
01/04/2008 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* |
01/07/2008 | RIGHT OF WAY - FINAL | MOTERO | Approved | PER EMAIL |
01/07/2008 | MECHANICAL - FINAL | MRAMBER | Approved | IVRS - Inspection :* |
01/08/2008 | ELECTRIC - PROGRESS | RJIROUDE | Approved | |
01/08/2008 | ELECTRIC - FINAL | RJIROUDE | Approved | IVRS - Inspection :* |
01/08/2008 | ELECTRIC - ABOVE CEILING | RJIROUDE | Approved | IVRS - Inspection :* |
01/09/2008 | PLUMBING - GAS PRESS TEST FNL | RMYERS | Approved | IVRS - Inspection :* |
01/09/2008 | PLUMBING - ABOVE CEILING | RMYERS | Approved | IVRS - Inspection :* |
01/11/2008 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* 1. NORMALLY I AFFIX THE GAS CARD TO THE HOUSE PIPING THERE IS NOT ENOUGH ROOM. DO NOT LOSE THIS CARD. 2. PLUMBING FINAL OK |
01/11/2008 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection :* |
01/11/2008 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection :* |
01/11/2008 | PLUMBING - PROGRESS | RMYERS | Approved | IVRS - Inspection :* |