Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03275
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/07/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ROOFTOP GFI REVERSE POLARITY WILL NOT TRIP 2. RECALL WHEN READY |
|
01/04/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ON ROOF: IDENTIFY AC'S - SERVICE RECEPTACLE REQUIRED WITHIN 25' OF UNITS - FLEX FOR STAT WIRE NOT SEALED STRAP FLEX WITHIN 12" OF ENCLOSURES - EQUIPMENT NOT TO BE IN FRONT OF DISCONNECTS - MUST KEEP WORKING CLEARANCES. 2. FINISH ALL PREVIOUS CORRECTIONS |
|
01/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. PANEL TO HAVE PROPER FRONT WORKING CLEARANCE - NEC 110.26 2. EMERGENCY LIGHTING TO BE PER NEC 700.12F 3. BURY GROUND RODS & G.E.C 4. PROVIDE ROOF ACCESS 5. STILL NEED TO REVISE PLANS TO SHOW ACTUAL SCOPE OF WORK, DO NOT CALL FOR ANOTHER INSPECTION BEFORE THIS HAS BEEN DONE. |