Permit: T07CM03275

Parcel: 124050620


Addresses:

922 E UNIVERSITY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/08/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/07/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROOFTOP GFI REVERSE POLARITY WILL NOT TRIP
2. RECALL WHEN READY
01/04/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ON ROOF: IDENTIFY AC'S - SERVICE RECEPTACLE REQUIRED WITHIN 25' OF UNITS - FLEX FOR STAT WIRE NOT SEALED
STRAP FLEX WITHIN 12" OF ENCLOSURES - EQUIPMENT NOT TO BE IN FRONT OF DISCONNECTS - MUST KEEP WORKING CLEARANCES.
2. FINISH ALL PREVIOUS CORRECTIONS
01/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. PANEL TO HAVE PROPER FRONT WORKING CLEARANCE - NEC 110.26
2. EMERGENCY LIGHTING TO BE PER NEC 700.12F
3. BURY GROUND RODS & G.E.C
4. PROVIDE ROOF ACCESS
5. STILL NEED TO REVISE PLANS TO SHOW ACTUAL SCOPE OF WORK, DO NOT CALL FOR ANOTHER INSPECTION BEFORE THIS HAS BEEN DONE.