Permit: T07CM03275

Parcel: 124050620


Addresses:

922 E UNIVERSITY BL

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
01/03/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
11/05/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- CONDENSATE PIPING TO BE INCREASED TO 1" WHERE TWO UNITS ARE "TEE" TOGETHER
- GP-1 PROVIDE DUCT SUPPORT ON 14" DUCT SO THAT FLEX CONNECTOR IS NOT USED FOR SUPPORT
- GP-2 PROVIDE DUCT SUPPORT ON BOTH 10" DUCT SO FLEX CONNECTOR IS NOT USED FOR SUPPORT