Permit: T07CM03275

Parcel: 124050620


Addresses:

922 E UNIVERSITY BL

Inspection Status: Approved

Inspection History: PLUMBING - ROOF DRAINS

Date Description Inspector Results Comments
01/04/2008 PLUMBING - ROOF DRAINS Approved IVRS - Inspection :*
01/03/2008 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
1. NO TEST ON GAS PIPING
2. STILL NO REDLINES THAT ARE READABLE
THEY ARE CALLED "REDLINES" BECAUSE THEY ARE TO BE RED

CONTRACTOR TO PAY REINSPECTION FEE
11/28/2007 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
1. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THREAD OF BRANCHES: THEN NO MORE THAN FOUR FEET BETWEEN HANGERS
2. NOT INSTALLED PER PLAN
ROOF DRAIN LOCATIONS AS REFERENCED ON A.1.3 ARE NOT ON THE PLUMBING PLAN - CHANGES TO THE PLAN MUST BE AUTHORIZED BY THE ENGINEER.
3. LAVATORY CARRIERS COVERED W/O INSPECTION
SEE NOTE ABOVE (11/13/07)
11/15/2007 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
TEST & SUPPORTS ON 4" RWC OK
PROVIDE PLAN FOR SIZING AND ROUTING
NOTE 180 DEG. CHANGE OF DIRECTION INSTALLED W/OUT CLEANOUTS