Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROOF DRAINS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2008 | PLUMBING - ROOF DRAINS | Approved | IVRS - Inspection :* | |
| 01/03/2008 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* 1. NO TEST ON GAS PIPING 2. STILL NO REDLINES THAT ARE READABLE THEY ARE CALLED "REDLINES" BECAUSE THEY ARE TO BE RED CONTRACTOR TO PAY REINSPECTION FEE |
|
| 11/28/2007 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* 1. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THREAD OF BRANCHES: THEN NO MORE THAN FOUR FEET BETWEEN HANGERS 2. NOT INSTALLED PER PLAN ROOF DRAIN LOCATIONS AS REFERENCED ON A.1.3 ARE NOT ON THE PLUMBING PLAN - CHANGES TO THE PLAN MUST BE AUTHORIZED BY THE ENGINEER. 3. LAVATORY CARRIERS COVERED W/O INSPECTION SEE NOTE ABOVE (11/13/07) |
|
| 11/15/2007 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* TEST & SUPPORTS ON 4" RWC OK PROVIDE PLAN FOR SIZING AND ROUTING NOTE 180 DEG. CHANGE OF DIRECTION INSTALLED W/OUT CLEANOUTS |