Permit: T07CM03275

Parcel: 124050620


Addresses:

922 E UNIVERSITY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM03275

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/08/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER
NO SERVICE/PANEL INSPECTION AT THIS TIME
11/13/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER ANGEL
11/09/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CORRECTIONS NOT COMPLETED
YOU WILL NEED TO PAY FEE IF NOT COMPLETE NEXT INSPECTION - DO NOT CALL BEFORE ALL PREVIOUS INSPECTIONS HAVE BEEN ADDRESSED.
11/06/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION:
1. MC TO BE SECURED WITHIN 12" OF TERMINATIONS AND SUPPORTED AT MAX 6' INTERVALS
2. ALL MC & WIRING TO BE PROTECTED WITH NAIL PLATES WHERE HOLE IS 1 1/4" OR LESS FROM STUD FACE
3. OLD WIRING/EQUIPMENT TO BE REMOVED
4. WIRING TO BE PER PLAN. IF NEEDED, REVISE PLAN TO SHOW ACTUAL SCOPE OF WORK
5. PROVIDE NAIL PLATE FOR NOTCHED OPENING
6. PLANS DO NOT SHOW A ONE LINE DIAGRAM, IS SERVICE AND PANEL NEW?
11/02/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE OLD WIRING & EQUIPMENT BEHIND WALLS
2. NEED NAIL PLATES WHERE HOLE IS 1 1/4" OR LESS TO STUD FACE
3. MC TO BE SUPPORTED @ MAX 6' INTERVALS
4. SECURE MC WITHIN 12" OF TERMINATIONS
5. MISSING MUD RINGS

PARTIAL INSPECTION ONLY
WORK NOT COMPLETE
DO NOT CALL BEFORE COMPLETE