Permit: T06CM03296
Permit Details
Apply Date:
06/02/2006
Applicant:
REIGLE, RICHARD MICHAEL
Description:
GROCERY STORE AND MARKET
Architects:
- REIGLE, RICHARD MICHAEL
Contractors:
- HAUGEBAK CONSTRUCTION COMPANY ,
Permit Reviews
Permit Number - T06CM03296
Permit Status: C of o
Permit Description: GROCERY STORE AND MARKET
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/20/2008 | 3RD PARTY REVIEW-REVISION/OTHER-2ND | 04/03/2008 | COMPLETED |
| 04/12/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 06/07/2007 | COMPLETED |
| 06/02/2006 | PLANS OK TO SUBMIT - 3RD PARTY | 06/02/2006 | COMPLETED |
| 06/02/2006 | SITE | 09/22/2006 | COMPLETED |
| 06/02/2006 | 3RD PARTY REVIEW-COMMERCIAL TI | 08/09/2006 | COMPLETED |
| 06/07/2007 | RESUBMITTAL | 07/03/2007 | COMPLETED |
| 07/14/2006 | OTHER | 08/09/2006 | COMPLETED |
| 08/09/2006 | POST 3RD PARTY REVIEW | 09/20/2006 | COMPLETED |
| 09/20/2006 | RESUBMITTAL | 09/22/2006 | COMPLETED |
| 09/22/2006 | RESUBMITTAL | 09/22/2006 | COMPLETED |
| 10/10/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 04/03/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM03296
Permit Status: C of o
Permit Description: GROCERY STORE AND MARKET
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/02/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T06CM03296
Permit Description: GROCERY STORE AND MARKET
Total Completed Inspections - 40
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2006 | STEM WALL/RETAINING WALL | AQUIROZ | Approved | IVRS - Inspection :* LOADING DOCK OK |
| 11/24/2006 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* CHECKED CONDENSATE IN WALL & RETURN DUCTS IN SPACE BEHIND DELI. OK TO COVER. SUSPENDED ROUGH DUCT OK TO PROCEED. |
| 12/06/2006 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | |
| 12/06/2006 | PLUMBING - ABOVE CEILING | RMYERS | Approved | IVRS - Inspection :* 1. DELI -- FROM COOKLINE WALL NORTH TO BAKERY OK TO COVER WALLS AND OVERHEAD. 2. GAS PRESSURE TEST OK 3. ROOF DRAINS AT NORTHWEST CORNER OK |
| 12/06/2006 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* |
| 12/06/2006 | PLUMBING - ROOF DRAINS | RMYERS | Approved | IVRS - Inspection :* |
| 12/09/2006 | PLUMBING - GAS PRESS TEST FNL | RMYERS | Approved | |
| 12/13/2006 | BUILDING PRE-SLAB | AQUIROZ | Approved | IVRS - Inspection :* AFTER HRS. INSP. $108.00 MONEY ORDER 0615136790 PARTIAL @ LINE 4.5-A |
| 12/13/2006 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* SOUTH & WEST WALL AT DELI SOUTH CORNER |
| 12/14/2006 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* CHECKED GREASE DUCTS IN DELI OK FOR FIRE WRAP SUSPENDED ROUGH DUCT BAKERY, DELI, SALES FLOOR OK TO PROCEED. |
| 12/14/2006 | PLUMBING - PRE SLAB | RMYERS | Approved | IVRS - Inspection :* 1. OK TO POUR SALES FLOOR 2. OK TO POUR BAKERY |
| 12/18/2006 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :* PLUMBING WALL IN MEAT DEPT. AT COOLER (EXPOSED) OK SUBJECT TO SPEC'S COPPER WATER SERVICE OK TO COVER |
| 12/18/2006 | PLUMBING - INTERMEDIATE | RMYERS | Approved | OK TO COVER WALL AT SEAFOOD PREP |
| 12/22/2006 | EXCAVATION/LAYOUT REBAR & ZON | AQUIROZ | Approved | IVRS - Inspection :* D.8-C.3 |
| 12/27/2006 | ELECTRIC - ABOVE CEILING | CCLEMENS | Approved | IVRS - Inspection :* |
| 12/28/2006 | REINFORCED MASONRY PRE-GROUT | AQUIROZ | Approved | IVRS - Inspection :* 1) 4' LIFT LOADING DECK, TOP OUT ? AREA |
| 12/28/2006 | ELECTRIC - INTERMEDIATE | CCLEMENS | Approved | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* INSPECTION FOR MEAT PREP AREA ONLY-FOR PURPOSE OF TEMPORARY USE: 1) CORD CAP RECEPTACLES TO BE RATED 20 AMP AND ATTACHED PROPERLY 2) CORRECTLY IDENTIFY ALL CKTS IN PANEL DIRECTORY 3) INSTALL MISSING K.O.'S IN BOXES AND REMOVE NOTCHES FOR IN USE COVERS 4) COILS TO HAVE MAXIMUM 15 AMP OVER CURRENT PROTECTION 5) STRANDED WIRE NOT ALLOWED UNDER SCREWS UNLESS LISTED 6) LIGHTING IS NOT PER PLAN/NOT EMERGENCY 7) INSTALL GASKETS ON ALL COVERS INCLUDES BLANKS 8) GO THROUGH ALL FRONT DISPLAY COOLERS-HAVE OPEN WIRING, UNGROUNDED BOXES, LOOSE FLEX CONNECTORS AND SLOPPY FLEX RUNS ETC. 2) PARTIAL INSPECTION ONLY-STILL NEED TO GO ON ROOF OF MEAT PREP AREA |
| 12/29/2006 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* 1) CHECKED EXHAUST DUCT IN MEAT PREP 2) FIRE WRAP AROUND CLEANOUT NOT SECURED PROPERLY 3) DO NOT USE TAPE TO HOLD WRAP TO DUCT 4) USE SPOT WELDED PINS AND SPEED CLIPS IN AREAS WHERE BONDING IS NOT POSSIBLE 5) NEED MORE WRAP AROUND ACCESS DOOR 6) STEEL PLATES MUST BE COMPLETELY TIGHT TO THE DUCT. WHY ARE THE EDGES BENT ? |
| 12/29/2006 | ELECTRIC - FINAL | CCLEMENS | Approved | IVRS - Inspection :* 1) OK TU USE MEAT PREP AREA-THIS AREA WILL BE SUBJECT TO INSPECTION AT FINAL |
| 01/25/2007 | ELECTRIC - CABLE DROP | CCLEMENS | Approved | CABLE DROP APPROVED 1/24/07 CALL BEFORE ANY FEEDERS ARE ENERGIZED. |
| 01/25/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER C. CLEMENS |
| 01/30/2007 | U VALUE FOR WINDOW | AQUIROZ | Approved | IVRS - Inspection :* |
| 01/30/2007 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection :* |
| 02/07/2007 | NPPO - FINAL | ACONNOR | Approved | |
| 02/07/2007 | LANDSCAPE - FINAL | ACONNOR | Approved | |
| 02/08/2007 | RIGHT OF WAY - FINAL | MOTERO | Approved | PER EMAIL |
| 02/16/2007 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
| 05/11/2007 | ROOF NAILING | AQUIROZ | Approved | IVRS - Inspection :* |
| 05/16/2007 | EXT METAL CLIPS/EXT SHEATHING | AQUIROZ | Approved | IVRS - Inspection :* |
| 06/01/2007 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* PLUMBING FINAL OK OK FOR C OF O |
| 06/05/2007 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 06/05/2007 | FIRE - FINAL | LTHOMAS | Approved | |
| 06/22/2007 | ENGINEERING - FINAL | MAVERY | Approved | See items on T06BU01679. |
| 08/04/2008 | OUTDOOR LIGHTING FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
| 08/04/2008 | ELECTRIC - OUTDOOR LIGHTING | RHOLLAND | Approved | IVRS - Inspection :* |
| 08/04/2008 | ELECTRIC - UFER | RHOLLAND | Approved | IVRS - Inspection :* |
| 08/14/2008 | SHEET ROCK NAILING | LHANLY | Approved | |
| 08/14/2008 | STUCCO MESH | LHANLY | Approved | |
| 08/14/2008 | SIGN - FINAL | LHANLY | Approved | |
| 08/22/2008 | BUILDING - FINAL | LHANLY | Approved |