Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM03296
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/16/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. AT EXTERIOR - DON'T TIE MC TO EMT, USE INDIVIDUAL STRAPS. 2. INTERIOR - HAVE EXCESSIVE MC - PROPERLY SUPPORT |
|
| 04/20/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILINGS EXCEPT FRONT ENTRANCE AREA |
|
| 04/16/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* INSPECTION FOR REMAINDER OF SALES FLOOR CEILING AREA 1. GRID SUPPORT WIRES NOT TO SUPPORT OTHER EQUIPMENT 2. EQUIPMENT SUPPORT WIRES TO BE SECURED AT BOTH ENDS 3. FINISH ALL WIRING, SUPPORT ALL WIRING OFF GRID 4. CLOSE OFF ALL UNUSED OPENINGS 5. FINISH DEMO, CHECK BOX FILL & GROUNDING 6. MAKE SURE ALL FIXTURES HAVE SUPPORT WIRES |
|
| 03/07/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 03/06/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* COMPLETE ALL WIRING AND DEMOLITION IN CEILINGS BEFORE INSPECTION, ALSO, CEILING TILES ARE NOT TO BE INSTALLED PRIOR TO APPROVAL. |
|
| 03/05/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 02/28/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 02/27/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 02/23/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 02/02/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK TO INSTALL CEILING TILES IN MAIN SALES FLOOR AREA 2) OK TO INSTALL CEILING TILES IN BAKERY PREP AREA |
|
| 02/01/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE WIRING/RACEWAYS (ALL) CLOSE OFF ENDS OF UNUSED RACEWAYS. REMOVE TEMP WIRING FOR CEILING INSPECTION |
|
| 12/27/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |