Permit: T06CM03296

Parcel: 10321341A


Addresses:

2140 W GRANT RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM03296

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/13/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) AIR BALANCE REPORT OK
2) OK FOR FINAL
06/06/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
EXTEND PRESSURE RELIEF FROM COMPRESSOR RACK UP THRU ROOF VENT & OUT ONTO ROOF
PROVIDE AIR BALANCE REPORT
05/08/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. WANT TO SEE RELIEF VALVES & PIPING ON RACH RECEIVERS
2. WHEN IS MINI-SPLIT CONDENSOR BEING FUSED? LEAVE PROPERLY BRACED
05/03/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
COMPLETE ELECT. TO COND.
WANT TO SEE RECEIVERS ON ROCKS RELIEF
VALVES AND PIPED TO DAYLIGHT
04/26/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
NEED TO SEE MINI-SPLIT SYSTEM COMPLETED.
EXTEND SEWER VENT 2' ABOVE MAU PERMANENTLY I.D ALL EQUIPMENT. PROVIDE DRAFT HOOD FOR MAU.
PROVIDE MIN. 1/4" PER FT. SLOPE ON WATER HEATER EXHAUST VENTS.
COVER CANVAS CONNECTOR.
02/08/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) CHECKED ABOVE CEILING IN BAKERY
2) OK FRO CEILING TILES
12/29/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) CHECKED EXHAUST DUCT IN MEAT PREP
2) FIRE WRAP AROUND CLEANOUT NOT SECURED PROPERLY
3) DO NOT USE TAPE TO HOLD WRAP TO DUCT
4) USE SPOT WELDED PINS AND SPEED CLIPS IN AREAS WHERE BONDING IS NOT POSSIBLE
5) NEED MORE WRAP AROUND ACCESS DOOR
6) STEEL PLATES MUST BE COMPLETELY TIGHT TO THE DUCT. WHY ARE THE EDGES BENT ?