Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM03296
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) AIR BALANCE REPORT OK 2) OK FOR FINAL |
|
| 06/06/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* EXTEND PRESSURE RELIEF FROM COMPRESSOR RACK UP THRU ROOF VENT & OUT ONTO ROOF PROVIDE AIR BALANCE REPORT |
|
| 05/08/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. WANT TO SEE RELIEF VALVES & PIPING ON RACH RECEIVERS 2. WHEN IS MINI-SPLIT CONDENSOR BEING FUSED? LEAVE PROPERLY BRACED |
|
| 05/03/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* COMPLETE ELECT. TO COND. WANT TO SEE RECEIVERS ON ROCKS RELIEF VALVES AND PIPED TO DAYLIGHT |
|
| 04/26/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* NEED TO SEE MINI-SPLIT SYSTEM COMPLETED. EXTEND SEWER VENT 2' ABOVE MAU PERMANENTLY I.D ALL EQUIPMENT. PROVIDE DRAFT HOOD FOR MAU. PROVIDE MIN. 1/4" PER FT. SLOPE ON WATER HEATER EXHAUST VENTS. COVER CANVAS CONNECTOR. |
|
| 02/08/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CHECKED ABOVE CEILING IN BAKERY 2) OK FRO CEILING TILES |
|
| 12/29/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CHECKED EXHAUST DUCT IN MEAT PREP 2) FIRE WRAP AROUND CLEANOUT NOT SECURED PROPERLY 3) DO NOT USE TAPE TO HOLD WRAP TO DUCT 4) USE SPOT WELDED PINS AND SPEED CLIPS IN AREAS WHERE BONDING IS NOT POSSIBLE 5) NEED MORE WRAP AROUND ACCESS DOOR 6) STEEL PLATES MUST BE COMPLETELY TIGHT TO THE DUCT. WHY ARE THE EDGES BENT ? |