Permit: T06CM03296

Parcel: 10321341A


Addresses:

2140 W GRANT RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM03296

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/20/2007 PLUMBING - INTERMEDIATE Approved OK TO COVER ALL AREAS
GAS IS ON
04/19/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
CORRECTIONS AT PRODUCE OK
04/13/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SUMP AT LOADING DOCK
LEFT GAS CARD
CORRECTION AT PRODUCE
04/11/2007 PLUMBING - INTERMEDIATE Partial Approval GAS SYSTEM COMPLETE
OK FOR GAS AT 2ND METER
WATER HEATER OK
04/05/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WELD PIPE NORTHEAST RECEIVING FROM OUTSIDE TO OVERHEAD OK CONNECTIONS NOT MADE YET
03/23/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ROOF DRAIN MAY NOT SPILL ONTO SIDEWALK -- PIPING OK
2. FLORAL & PRODUCE OK
OK TO COVER WALLS
OK TO COVER OVERHEAD
03/20/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SOUTHEAST CLOSET FLANGES OK
03/09/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PUBLIC RESTROOMS
ABS DWV OK
WATER TEST OK
COPPER OK
OK TO COVER WALLS
NEED TO SEE FLANGES
03/07/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ROOF DRAINS AT RECEIVING #116 OK
2. UNISEX TOILET ROOMS COMPLETE
3. OK TO COVER WALLS AT PRODUCE
4. 2 FLOOR SINKS INSTALLED AT DISPLAY CASES
02/28/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PHARMACY SINK OK
ABS
COPPER
2. STARBUCKS READY TO OCCUPY S.T.O.I
02/23/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
HOLD OVER TO 2/23/07 PER CONTRACTOR

STARBUCKS
1. SHALL HAVE CORRECT DRAINAGE FOR HAND SINK
2. HAVE BACKFLOW CERTIFICATIONS & ALL EQUIPMENT INSTALLED.

BAKERY - GAS PIPING TO RELOCATED OVEN OK
CONTRACTOR TO ENERGIZE AND VERIFY NO LEAKAGE OF GAS AT FINAL CONNECTION.
02/21/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WASTE & VENT WATER TEST THRU ROOF IN STARBUCKS OK
WATER PIPING OK
CONDENSATES FROM A - 3 & 4 & MAV #1 OK
10 PSI TEST FROM APPLIANCE SHUT OFF VALVES FOR AC-3, AC-4, MAV-1 TO CAP AT UNIT OK

CONTRACTOR TO MAKE FINAL CONNECTION VERIFY NO LEAKAGE AT TIME OF ENERGIZING.
02/07/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/01/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/24/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/19/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/10/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. 3/4 GAS STUB UP TO CEILING FOR PAN WASHER
AIR TEST OK
2. WASTE & VENT NORTH WALL & SOUTH WALL TO 12' AFF IN BAKERY AREA WATER TEST OK
3. WATER PIPING IN WALL, NORTHWALL OF BAKERY ONLY OK
12/18/2006 PLUMBING - INTERMEDIATE Partial Approval OK TO COVER WALL AT SEAFOOD PREP
12/15/2006 PLUMBING - INTERMEDIATE Partial Approval OK TO COVER WALLS TO ABOVE CEILING AT DELI AND BEVERAGE STATION.
12/13/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. BAKERY UNDERGROUND OK TO COVER
2. MEAT PREP WALLS OK TO COVER
3. CONTRACTOR REQUESTS AFTER HOURS INSPECTION
FOR 8:00 PM
12/13/2006 PLUMBING - INTERMEDIATE Partial Approval PAID WITH MONEY GRAM 5587441105 FOR $108.00

1. GREASE WASTE FOR BAKERY AND TIED INTO PREVIOUSLY INSPECTED SECTION OK TO COVER.
2. CONTRACTOR TO REDLINE CHANGES TO THE PLAN.
11/27/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. 1 1/2" GAS, WATER AND WASTE IN NORTH DELI WALL STUB OUTS OK. VTR OK AT FS-2 RECEIVING AC CONDENSATE.
2. WATER, WASTE & VENT IN WALLS AT NW CORNER CAKE DECORATING AREAS OK TO COVER WALLS.
11/23/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DELI AREA INSIDE OK TO COVER
2) AT SOFTNER AND AT WATER HEATER FLOOR SINK AND VENTS NORTH OF DELI
11/21/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/19/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
3" VENTS LED BACK INTO EXISTING COLUMN ALONG COLUMN "D" OK FOR CASES