Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM03296
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2007 | PLUMBING - INTERMEDIATE | Approved | OK TO COVER ALL AREAS GAS IS ON |
|
| 04/19/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* CORRECTIONS AT PRODUCE OK |
|
| 04/13/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUMP AT LOADING DOCK LEFT GAS CARD CORRECTION AT PRODUCE |
|
| 04/11/2007 | PLUMBING - INTERMEDIATE | Partial Approval | GAS SYSTEM COMPLETE OK FOR GAS AT 2ND METER WATER HEATER OK |
|
| 04/05/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WELD PIPE NORTHEAST RECEIVING FROM OUTSIDE TO OVERHEAD OK CONNECTIONS NOT MADE YET |
|
| 03/23/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. ROOF DRAIN MAY NOT SPILL ONTO SIDEWALK -- PIPING OK 2. FLORAL & PRODUCE OK OK TO COVER WALLS OK TO COVER OVERHEAD |
|
| 03/20/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SOUTHEAST CLOSET FLANGES OK |
|
| 03/09/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PUBLIC RESTROOMS ABS DWV OK WATER TEST OK COPPER OK OK TO COVER WALLS NEED TO SEE FLANGES |
|
| 03/07/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. ROOF DRAINS AT RECEIVING #116 OK 2. UNISEX TOILET ROOMS COMPLETE 3. OK TO COVER WALLS AT PRODUCE 4. 2 FLOOR SINKS INSTALLED AT DISPLAY CASES |
|
| 02/28/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PHARMACY SINK OK ABS COPPER 2. STARBUCKS READY TO OCCUPY S.T.O.I |
|
| 02/23/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* HOLD OVER TO 2/23/07 PER CONTRACTOR STARBUCKS 1. SHALL HAVE CORRECT DRAINAGE FOR HAND SINK 2. HAVE BACKFLOW CERTIFICATIONS & ALL EQUIPMENT INSTALLED. BAKERY - GAS PIPING TO RELOCATED OVEN OK CONTRACTOR TO ENERGIZE AND VERIFY NO LEAKAGE OF GAS AT FINAL CONNECTION. |
|
| 02/21/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WASTE & VENT WATER TEST THRU ROOF IN STARBUCKS OK WATER PIPING OK CONDENSATES FROM A - 3 & 4 & MAV #1 OK 10 PSI TEST FROM APPLIANCE SHUT OFF VALVES FOR AC-3, AC-4, MAV-1 TO CAP AT UNIT OK CONTRACTOR TO MAKE FINAL CONNECTION VERIFY NO LEAKAGE AT TIME OF ENERGIZING. |
|
| 02/07/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 02/01/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 01/24/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 01/19/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/10/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. 3/4 GAS STUB UP TO CEILING FOR PAN WASHER AIR TEST OK 2. WASTE & VENT NORTH WALL & SOUTH WALL TO 12' AFF IN BAKERY AREA WATER TEST OK 3. WATER PIPING IN WALL, NORTHWALL OF BAKERY ONLY OK |
|
| 12/18/2006 | PLUMBING - INTERMEDIATE | Partial Approval | OK TO COVER WALL AT SEAFOOD PREP | |
| 12/15/2006 | PLUMBING - INTERMEDIATE | Partial Approval | OK TO COVER WALLS TO ABOVE CEILING AT DELI AND BEVERAGE STATION. | |
| 12/13/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. BAKERY UNDERGROUND OK TO COVER 2. MEAT PREP WALLS OK TO COVER 3. CONTRACTOR REQUESTS AFTER HOURS INSPECTION FOR 8:00 PM |
|
| 12/13/2006 | PLUMBING - INTERMEDIATE | Partial Approval | PAID WITH MONEY GRAM 5587441105 FOR $108.00 1. GREASE WASTE FOR BAKERY AND TIED INTO PREVIOUSLY INSPECTED SECTION OK TO COVER. 2. CONTRACTOR TO REDLINE CHANGES TO THE PLAN. |
|
| 11/27/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. 1 1/2" GAS, WATER AND WASTE IN NORTH DELI WALL STUB OUTS OK. VTR OK AT FS-2 RECEIVING AC CONDENSATE. 2. WATER, WASTE & VENT IN WALLS AT NW CORNER CAKE DECORATING AREAS OK TO COVER WALLS. |
|
| 11/23/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DELI AREA INSIDE OK TO COVER 2) AT SOFTNER AND AT WATER HEATER FLOOR SINK AND VENTS NORTH OF DELI |
|
| 11/21/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 10/19/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3" VENTS LED BACK INTO EXISTING COLUMN ALONG COLUMN "D" OK FOR CASES |