Permit: T06CM03296

Parcel: 10321341A


Addresses:

2140 W GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM03296

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/04/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/01/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
07/10/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH VDV CABLING PER 725.6 AND 300.11
07/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CALLED PH# PER REQUEST, LEFT MESSAGE, RECALL INSPECTION, COULD NOT LOCATE CONTR. ON SITE.
06/19/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/10/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY
1. POST LABELS AT PANELS PER NEC 200.6D & 210.5C
2. NEED PLAN REVIEW FOR ENCLOSED ROOM BUILT ABOVE CEILING FOR BREAK ROOM. PLAN TO SHOW EQUIPMENT
AS IT IS INSTALLED. EQUIPMENT CLEARANCES TO BE
PER NEC 110.26
ALSO, REMOVE PAINT UNDER LUGS, DO NOT STACK LUGS.
3. ALL LOW VOLTAGE WIRING IN CEILINGS TO BE PROPERLY SUPPORTED TO STRUCTURE, NOT TO LAY ON GRID OR OTHER EQUIPMENT
4. CHECK/RETYPE PANEL DIRECTORIES SF & R3 - ABBREVIATIONS NOT ALLOWED/GO TO WHAT IS SAYS
06/04/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR UPS INSTALLATION -
PARTIAL INSPECTION ONLY

1. PLAN SHOWS U.P.S MOUNTED 10' AFF RIGHT NOW IT IS BLOCKING ACCESS TO EQUIPMENT
2. THIS IS NOT A UPS SIZE SHOWN ON PLANS - NOT WIRED PER PLAN
3. DISCONNECTS & SWITCHES FOR UPS TO BE MAX. 6'7" TO SWITCHES ABOVE FLOOR (IN UP/ON POSITION)
4. A SIGN IS REQUIRED AT SERVICE FOR UPS AND GENERATOR
SEE NEC 700.8
5. OVERCURRENT PROTECTION NOT CORRECTLY SIZED
6. NEED BUSHINGS FOR FITTING WITH #4 & LARGER CONDUCTORS
7. IDENTIFY ALL DISCONNECTS
8. CORDS NOT TO TAKE THE PLACE OF PERMANENT WIRING METHODS.
9. 2 GROUNDS NOT ALLOWED UNDER SAME LUG IN J-BOX
06/03/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/14/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
WIRING TO BE DONE PER PLAN AND PER CODE,
ELECTRICAL CONTRACTOR TO GO THROUGH ENTIRE INSTALLATION BEFORE CALLING FOR FINAL.

ALSO, MAKE SURE ALL PREVIOUS CORRECTIONS COMPLETE
04/09/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/01/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO INSPECTION AT THIS TIME

1. WORK NOT PER APPROVED PLAN - REVISE PLAN AND GET PLAN REVIEW APPROVAL
2. ELECTRICIAN WILL BE REQUIRED FOR INSPECTIONS TO OPEN EQUIPMENT
3. WILL NEED INSTALLATION MANUAL FOR GENERATOR
4. WHEN YOU HAVE APPROVED PLANS, HAVE ELECTRICAL CONTRACTOR GO THROUGH WORK AND MAKE SURE INSTALLATION IS PER PLAN AND PER CODE, THEN CALL FOR FINALS.
09/24/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
09/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/27/2007 ELECTRIC - FINAL Cancelled CANCELLED PER BEN OF HAUGEBAK CONST. #955-3809
08/27/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
06/11/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO INSPECTION AT THIS TIME
ALL WORK AND PREVIOUS CORRECTIONS TO BE COMPLETE
BEFORE A FINAL INSPECTION IS CALLED IN.
02/21/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
02/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
INSPECTION FOR MAIN SALES AREA OF ADDITION,
INTERIOR ONLY

1. INSTALL PANEL DIRECTORY FOR PANELS "DA & DB"

OK TO OCCUPY ADDITION AREA - EXTERIOR EGRESS LIGHTING NOT COMPLETE. THERE WILL BE NO FINAL APPROVALS UNTIL ELECTRICAL WORK IS COMPLETE. THIS IS A PARTIAL INSPECTION ONLY AND ALL AREAS WILL BE SUBJECT TO INSPECTION ON ELECTRICAL FINAL.
02/16/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
OK TO COVER UNDERGROUND
FOR STARBUCKS AREA
AND IN CLOSET WALL
02/15/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CALL FOR FINAL WHEN COMPLETE
ADDITION NOT TO BE OCCUPIED
PRIOR TO APPROVAL BY THE BUILDING OFFICIAL FOR THE CITY OF TUCSON.
02/08/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) INSPECTION FOR TCO FOR ADDITION
2) THIS AREA IS NOT READY FOR TCO INSPECTION
12/29/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) OK TU USE MEAT PREP AREA-THIS AREA WILL BE SUBJECT TO INSPECTION AT FINAL