Permit: T06CM03296

Parcel: 10321341A


Addresses:

2140 W GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM03296

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/04/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/27/2007 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
CANCELLED PER BEN OF HAUGEBAK CONST. #955-3809
08/27/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
05/04/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
AGREE WITH CALL OF 4/26/07 WITH C.CLEMENS TRANSFORMERS OVER 50KVA CANNOT BE ABOVE CEILING
04/26/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR TRANSFORMERS ABOVE BREAKROOM CEILING
1. 75 KVA TRANSFORMERS NOT ALLOWED TO BE INSTALLED IN CEILING AREA ABOVE BREAK ROOM BATHROOMS. I CONSIDER THIS AREA A "HOLLOW SPACE" IN THE BUILDING NEC 450.13B
ALSO, HAVE PREVIOUS CORRECTIONS FOR INSTALLATION
SEE REPORT FOR 3/22/07

TRANSFORMERS IN QUESTION ARE 75KVA DRY TYPE
03/22/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR BREAKROOM PANELS "R3 & SF" ONLY
BRANCH CKT'S NOT ALL IN YET.

1. IDENTIFY DISCONNECTS
2. BONDING CLAMP TO BE ACCESSIBLE (TRANSFORMER TO WATER)
3. BOND WIRE T3 INTO DISCONNECT UNDERSIZED --
NEC 250.30 A5
4. #6 AND SMALLER EQUIPMENT GROUND GREEN OR BARE ENTIRE LENGTH NEC 250.119
5. SECURE TRANSFORMER TO STRUCTURE - NEC 110.13
6. INSTALL FUSES (7) NEUTRAL NOT TO BOND TO DISCONNECT ENCLOSURE -- NEC 250.30
7. REMOVE PAINT UNDERGROUND LUGS (8) CHECK TRANSFORMER LOCATION -- NEC 450 75 KVA
03/15/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER EMPLOYEE LOUNGE
03/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK C OF O PHARMACY
03/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER BATHROOMS, ICC ROOM
OK TO OCCUPY PHARMACY - THIS AREA WILL BE SUBJECT TO A FINAL INSPECTION AT A LATER DATE.
03/07/2007 ELECTRIC - INTERMEDIATE Partial Approval OK TO COVER FLORAL EAST EXT. WALLS
OK CEILING TILES C3-4 LINES
03/06/2007 ELECTRIC - INTERMEDIATE Cancelled IVRS - AP canceled
02/28/2007 ELECTRIC - INTERMEDIATE Partial Approval 1. FOR FINAL ON STARBUCKS - PERMANENTLY MARK DISCONNECT A PNL RD
OK STARBUCKS KIOSK FOR OCCUPANCY & TRAINING
2. OK TO COVER PRODUCE WASH WALLS, TWO
02/27/2007 ELECTRIC - INTERMEDIATE Partial Approval PARTIAL - OK PHARMACY
02/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER FRONT EXTERIOR CANOPY -
CENTER /WEST PROVIDE ACCESS OPENING TO THIS CANOPY FOR ACCESS TO J-BOXES
02/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/15/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/07/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) WORK IN PROGRESS-SAFE OFF ALL OPEN WIRING, PANELS ETC... IF NOT ATTENDED
01/31/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/30/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSPECTION FOR SERVICE IN ANTICIPATION OF SWITCHOVER FROM OLD SERVICE TO NEW SERVICE:
1. PERFORMANCE TEST FOR SERVICE (NEC 230.95(C)) PROVIDE A WRITTEN LETTER FROM TESTING AGENCY THAT STATES THAT THE TEST WAS PERFORMED IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS AND RESULTS OF TEST (PASS OR FAIL)
2. NORTH END OF SERVICE IS OFF SLAB
3. PROVIDE LETTER OF TORQUE FOR SERVICE
4. COMPLETE FEEDER/BONDING TERMINATIONS AS FAR AS POSSIBLE BEFORE SWITCHOVER.

CALL FOR INSPECTION WHEN ABOVE IS COMPLETE
01/22/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
COULD NOT GET IVR MESSAGE, NO ELECT ON SITE
01/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER UNDER FLOOR RACEWAYS TO REGISTER AREAS
PLEASE PROVIDE INFORMATION ON UNDER FLOOR RACEWAYS
01/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSPECTION FOR BAKERY PREP AREA
1. INSTALL PROPER SIZE CLAMPS FOR FEEDER RACEWAYS
2. REMOVE TEMP. WIRING
OK TO COVER WALL FOR PANELS "BA" "BB" & "TA" AFTER CORRECTIONS.

NOTE: PROVIDE GFI PROTECTION FOR 120V CONSTRUCTION RECEPTACLES (ALL)

INSPECTION FOR SERVICE ONLY - PARTIAL INSPECTION
1. INSTALL ADDRESS ON SERVICE
2. INSTALL MAIN BONDING JUMPER FOR SERVICE -
NEC 110.3B, 250.24
3. PROVIDE PERFORMANCE TEST FOR SERVICE - NEC 230.95 C
4. PROVIDE PROTECTION ON SECONDARY PVC ENDS -
NEC 352.46
5. CONDUCTORS IN SERVICE NOT TO CROSS SECTIONS -
NEC 408.3
6. PROVIDE A LETTER OF TORQUE FOR SERVICE
7. BOND ALL METAL PIPING SYSTEMS TO SERVICE -
NEC 250.104
8. CHECK TO SEE IF BOX ABOVE SERVICE IS CORRECTLY SIZED OR NEEDS TO BE DERATED - PROVIDE CALCULATIONS
NEC 314.28, NEC 366.6
9. 480V/277V RACEWAYS ELECTRICAL CONTINUITY TO BE PER NEC 250.97 - VERIFY THIS TYPE OF MYERS HUB LISTED FOR OVER 250V
10. NEED BUSHINGS FOR CONDUCTORS #4 AND LARGER
NEC 300.4 F
11. GROUND ALL ENCLOSURES WITH PROPERLY SIZED EQUIPMENT GROUND - NEC 250.122
12. IDENTIFY ALL DISCONNECTS - NEC 110.22
13. FINISH ALL WIRING/FEEDERS TO SERVICE
01/11/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSPECTION FOR BAKERY PREP AREA ONLY
1. OK TO COVER ELECTRICAL IN NORTH WALL
2. OK TO COVER ELECTRICAL IN SW WALL (NOT PANEL AREAS)
12/28/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR MEAT PREP AREA ONLY-FOR PURPOSE OF TEMPORARY USE:
1) CORD CAP RECEPTACLES TO BE RATED 20 AMP AND ATTACHED PROPERLY
2) CORRECTLY IDENTIFY ALL CKTS IN PANEL DIRECTORY
3) INSTALL MISSING K.O.'S IN BOXES AND REMOVE NOTCHES FOR IN USE COVERS
4) COILS TO HAVE MAXIMUM 15 AMP OVER CURRENT PROTECTION
5) STRANDED WIRE NOT ALLOWED UNDER SCREWS UNLESS LISTED
6) LIGHTING IS NOT PER PLAN/NOT EMERGENCY
7) INSTALL GASKETS ON ALL COVERS INCLUDES BLANKS
8) GO THROUGH ALL FRONT DISPLAY COOLERS-HAVE OPEN WIRING, UNGROUNDED BOXES, LOOSE FLEX CONNECTORS AND SLOPPY FLEX RUNS ETC.
2) PARTIAL INSPECTION ONLY-STILL NEED TO GO ON ROOF OF MEAT PREP AREA
12/27/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
PROVIDE SEALED LETTER FROM ENGINEER OF RECORD CONCERNING ANY MINOR REVISIONS TO PLANS.
12/22/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
FRONT OFFICES OK
MDF ROOM OK
CASH OFFICE OK
12/13/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
TOM (602) 725-0585
SHAWN (520) 592-2916

OK DELI WALLS, FLOOR DUCT RETAIL AREAS FOR GONDOLAS
NOTE: BACK BRACE BOXES AS NEEDED AND INSTALL K.O SEAL
11/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER DELI AREA PANELS "DA" & "DB"
OK UNDERGROUND FEEDERS TO PANEL "BA" & "BB"
11/22/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WEST WALL COVER
2) OK NORTH WAL COVER AT GUTTER RACEWAYS
3) NOTE: PROVIDE BACK SUPPORT FOR RECEPTACLE BOXES AS NEEDED AND STRAP RACEWAYS INTO GUTTER WITHIN 3' OF GUTTER AND GRADE
11/20/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SERVICE GROUND RODS/SECONDARY
OK DELI HOOD WALL.
11/15/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/01/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NEST SLAB AREA UNDERGROUND -- FEEDERS, BRANCH CKTS.