Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM03296
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/27/2007 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled CANCELLED PER BEN OF HAUGEBAK CONST. #955-3809 |
|
| 08/27/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |
|
| 05/04/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* AGREE WITH CALL OF 4/26/07 WITH C.CLEMENS TRANSFORMERS OVER 50KVA CANNOT BE ABOVE CEILING |
|
| 04/26/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR TRANSFORMERS ABOVE BREAKROOM CEILING 1. 75 KVA TRANSFORMERS NOT ALLOWED TO BE INSTALLED IN CEILING AREA ABOVE BREAK ROOM BATHROOMS. I CONSIDER THIS AREA A "HOLLOW SPACE" IN THE BUILDING NEC 450.13B ALSO, HAVE PREVIOUS CORRECTIONS FOR INSTALLATION SEE REPORT FOR 3/22/07 TRANSFORMERS IN QUESTION ARE 75KVA DRY TYPE |
|
| 03/22/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR BREAKROOM PANELS "R3 & SF" ONLY BRANCH CKT'S NOT ALL IN YET. 1. IDENTIFY DISCONNECTS 2. BONDING CLAMP TO BE ACCESSIBLE (TRANSFORMER TO WATER) 3. BOND WIRE T3 INTO DISCONNECT UNDERSIZED -- NEC 250.30 A5 4. #6 AND SMALLER EQUIPMENT GROUND GREEN OR BARE ENTIRE LENGTH NEC 250.119 5. SECURE TRANSFORMER TO STRUCTURE - NEC 110.13 6. INSTALL FUSES (7) NEUTRAL NOT TO BOND TO DISCONNECT ENCLOSURE -- NEC 250.30 7. REMOVE PAINT UNDERGROUND LUGS (8) CHECK TRANSFORMER LOCATION -- NEC 450 75 KVA |
|
| 03/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER EMPLOYEE LOUNGE |
|
| 03/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK C OF O PHARMACY |
|
| 03/09/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER BATHROOMS, ICC ROOM OK TO OCCUPY PHARMACY - THIS AREA WILL BE SUBJECT TO A FINAL INSPECTION AT A LATER DATE. |
|
| 03/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | OK TO COVER FLORAL EAST EXT. WALLS OK CEILING TILES C3-4 LINES |
|
| 03/06/2007 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - AP canceled | |
| 02/28/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. FOR FINAL ON STARBUCKS - PERMANENTLY MARK DISCONNECT A PNL RD OK STARBUCKS KIOSK FOR OCCUPANCY & TRAINING 2. OK TO COVER PRODUCE WASH WALLS, TWO |
|
| 02/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | PARTIAL - OK PHARMACY | |
| 02/23/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER FRONT EXTERIOR CANOPY - CENTER /WEST PROVIDE ACCESS OPENING TO THIS CANOPY FOR ACCESS TO J-BOXES |
|
| 02/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 02/15/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/07/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) WORK IN PROGRESS-SAFE OFF ALL OPEN WIRING, PANELS ETC... IF NOT ATTENDED |
|
| 01/31/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/30/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/23/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSPECTION FOR SERVICE IN ANTICIPATION OF SWITCHOVER FROM OLD SERVICE TO NEW SERVICE: 1. PERFORMANCE TEST FOR SERVICE (NEC 230.95(C)) PROVIDE A WRITTEN LETTER FROM TESTING AGENCY THAT STATES THAT THE TEST WAS PERFORMED IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS AND RESULTS OF TEST (PASS OR FAIL) 2. NORTH END OF SERVICE IS OFF SLAB 3. PROVIDE LETTER OF TORQUE FOR SERVICE 4. COMPLETE FEEDER/BONDING TERMINATIONS AS FAR AS POSSIBLE BEFORE SWITCHOVER. CALL FOR INSPECTION WHEN ABOVE IS COMPLETE |
|
| 01/22/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* COULD NOT GET IVR MESSAGE, NO ELECT ON SITE |
|
| 01/19/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER UNDER FLOOR RACEWAYS TO REGISTER AREAS PLEASE PROVIDE INFORMATION ON UNDER FLOOR RACEWAYS |
|
| 01/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSPECTION FOR BAKERY PREP AREA 1. INSTALL PROPER SIZE CLAMPS FOR FEEDER RACEWAYS 2. REMOVE TEMP. WIRING OK TO COVER WALL FOR PANELS "BA" "BB" & "TA" AFTER CORRECTIONS. NOTE: PROVIDE GFI PROTECTION FOR 120V CONSTRUCTION RECEPTACLES (ALL) INSPECTION FOR SERVICE ONLY - PARTIAL INSPECTION 1. INSTALL ADDRESS ON SERVICE 2. INSTALL MAIN BONDING JUMPER FOR SERVICE - NEC 110.3B, 250.24 3. PROVIDE PERFORMANCE TEST FOR SERVICE - NEC 230.95 C 4. PROVIDE PROTECTION ON SECONDARY PVC ENDS - NEC 352.46 5. CONDUCTORS IN SERVICE NOT TO CROSS SECTIONS - NEC 408.3 6. PROVIDE A LETTER OF TORQUE FOR SERVICE 7. BOND ALL METAL PIPING SYSTEMS TO SERVICE - NEC 250.104 8. CHECK TO SEE IF BOX ABOVE SERVICE IS CORRECTLY SIZED OR NEEDS TO BE DERATED - PROVIDE CALCULATIONS NEC 314.28, NEC 366.6 9. 480V/277V RACEWAYS ELECTRICAL CONTINUITY TO BE PER NEC 250.97 - VERIFY THIS TYPE OF MYERS HUB LISTED FOR OVER 250V 10. NEED BUSHINGS FOR CONDUCTORS #4 AND LARGER NEC 300.4 F 11. GROUND ALL ENCLOSURES WITH PROPERLY SIZED EQUIPMENT GROUND - NEC 250.122 12. IDENTIFY ALL DISCONNECTS - NEC 110.22 13. FINISH ALL WIRING/FEEDERS TO SERVICE |
|
| 01/11/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/10/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSPECTION FOR BAKERY PREP AREA ONLY 1. OK TO COVER ELECTRICAL IN NORTH WALL 2. OK TO COVER ELECTRICAL IN SW WALL (NOT PANEL AREAS) |
|
| 12/28/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* INSPECTION FOR MEAT PREP AREA ONLY-FOR PURPOSE OF TEMPORARY USE: 1) CORD CAP RECEPTACLES TO BE RATED 20 AMP AND ATTACHED PROPERLY 2) CORRECTLY IDENTIFY ALL CKTS IN PANEL DIRECTORY 3) INSTALL MISSING K.O.'S IN BOXES AND REMOVE NOTCHES FOR IN USE COVERS 4) COILS TO HAVE MAXIMUM 15 AMP OVER CURRENT PROTECTION 5) STRANDED WIRE NOT ALLOWED UNDER SCREWS UNLESS LISTED 6) LIGHTING IS NOT PER PLAN/NOT EMERGENCY 7) INSTALL GASKETS ON ALL COVERS INCLUDES BLANKS 8) GO THROUGH ALL FRONT DISPLAY COOLERS-HAVE OPEN WIRING, UNGROUNDED BOXES, LOOSE FLEX CONNECTORS AND SLOPPY FLEX RUNS ETC. 2) PARTIAL INSPECTION ONLY-STILL NEED TO GO ON ROOF OF MEAT PREP AREA |
|
| 12/27/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PROVIDE SEALED LETTER FROM ENGINEER OF RECORD CONCERNING ANY MINOR REVISIONS TO PLANS. |
|
| 12/22/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FRONT OFFICES OK MDF ROOM OK CASH OFFICE OK |
|
| 12/13/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* TOM (602) 725-0585 SHAWN (520) 592-2916 OK DELI WALLS, FLOOR DUCT RETAIL AREAS FOR GONDOLAS NOTE: BACK BRACE BOXES AS NEEDED AND INSTALL K.O SEAL |
|
| 11/27/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER DELI AREA PANELS "DA" & "DB" OK UNDERGROUND FEEDERS TO PANEL "BA" & "BB" |
|
| 11/22/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WEST WALL COVER 2) OK NORTH WAL COVER AT GUTTER RACEWAYS 3) NOTE: PROVIDE BACK SUPPORT FOR RECEPTACLE BOXES AS NEEDED AND STRAP RACEWAYS INTO GUTTER WITHIN 3' OF GUTTER AND GRADE |
|
| 11/20/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK SERVICE GROUND RODS/SECONDARY OK DELI HOOD WALL. |
|
| 11/15/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 11/01/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NEST SLAB AREA UNDERGROUND -- FEEDERS, BRANCH CKTS. |