Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Apply Date:
11/21/2005
Applicant:
SBBL - CAROLYN URIAS
Description:
TI:MEDICAL OFFICE REV 3: 85 FIXTURE UNIT CREDIT PER REV 3: 27 USED FOR T06CM02576: 23 REMAIN
Architects:
  • SBBL ARCHITECTURE + PLANNING
Contractors:
  • FINA COMPANIES L L C

Permit Reviews

Permit Number - T05CM05829
Permit Status: C of o
Permit Description: TI:MEDICAL OFFICE REV 3: 85 FIXTURE UNIT CREDIT PER REV 3: 27 USED FOR T06CM02576: 23 REMAIN
Start Date Submittal Complete Date Status  
03/22/2007 REVISION - SITE 03/22/2007 COMPLETED Review Details
03/23/2007 REVISION - - 3RD 03/26/2007 COMPLETED Review Details
04/09/2007 3RD PARTY REVIEW-REVISION/OTHER 04/09/2007 COMPLETED Review Details
05/18/2007 REVISION - - 4TH 05/18/2007 COMPLETED Review Details
08/14/2006 3RD PARTY REVIEW-REVISION/OTHER 08/14/2006 COMPLETED Review Details
09/06/2006 3RD PARTY REVIEW-REVISION/OTHER 09/12/2006 COMPLETED Review Details
09/20/2006 3RD PARTY REVIEW-REVISION/OTHER 09/20/2006 COMPLETED Review Details
11/21/2005 PLANS OK TO SUBMIT - 3RD PARTY 11/21/2005 COMPLETED Review Details
11/21/2005 3RD PARTY REVIEW-COMMERCIAL TI 12/13/2005 COMPLETED Review Details
12/13/2005 POST 3RD PARTY REVIEW 02/01/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM05829
Permit Status: C of o
Permit Description: TI:MEDICAL OFFICE REV 3: 85 FIXTURE UNIT CREDIT PER REV 3: 27 USED FOR T06CM02576: 23 REMAIN
Total Outstanding Activity Conditions - 1
Date Name
11/21/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T05CM05829
Permit Description: TI:MEDICAL OFFICE REV 3: 85 FIXTURE UNIT CREDIT PER REV 3: 27 USED FOR T06CM02576: 23 REMAIN
Total Completed Inspections - 26
Date Description Inspector Results Comments
09/19/2006 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection :*
09/19/2006 FRAMING GDABBS Approved IVRS - Inspection :*
09/20/2006 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
SUPPLY & EXHAUST IN HARD LID AREAS OK FOR SHEETROCK
PLANS REQUIRE 1 1/2" DUCT LINER & 2" DUCT WRAP.
PROVIDE REVISION IF CHANGING FROM APPROVED PLANS.
10/18/2006 SHEET ROCK NAILING GDABBS Approved IVRS - Inspection :*
LOBBY/ENTRY AREA OK TO TAPE
12/18/2006 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
OK FOR CEILING TILES
12/18/2006 PLUMBING - INTERMEDIATE RRICH Approved IVRS - Inspection :*
REVISED APPROVED PLAN ON SITE
12/18/2006 PLUMBING - ROUGH, SOIL RRICH Approved IVRS - Inspection :*
REVISED APPROVED PLAN ON SITE
12/18/2006 BUILDING ABOVE CEILING GDABBS Approved IVRS - Inspection :*
12/26/2006 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :*
1. FINISH ATTACHING BOTTOM ENDS FOR VDV CABELING 300.11
2. MAINTAIN CLEARANCES FOR DISCONNECT ABOVE CEILING.
3. SUPPORT CABLES UPON EXITING CABLE TRAY 392.6
4. PLEASE VERIFY CABLE TRAY BOND PER 392.6 & 7

OK 2X2 FIXTURES
12/27/2006 PLUMBING - ABOVE CEILING RRICH Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) PAY REFEE, COMPLETE INSULATION AS REQUESTED THEN CALL FOR ABOVE CEILING INSPECTION
2) NO FINAL INSPECTION UNTIL REFEE IS PAID
3) 5 DAYS TO PAY UNTIL PERMIT SHALL BE FROZEN FOR INSPECTIONS
01/18/2007 ELECTRIC - TEMP POWER FOR TEST RMAJUTA Approved IVRS - Inspection :*
OK TO CLEAR
01/18/2007 ELECTRIC - CABLE DROP RMAJUTA Approved IVRS - Inspection :*
NOTE: SECTION 110-26A NEC 2002 REQUIRES A DEPTH OF 3' IN FRONT OF THE SERVICE SWITCH GEAR, THIS AREA IS FOR THE SAFETY OF MAINTENANCE AND EXAMINATION OF THE SWITCH GEAR. THIS AREA HAS TO BE THE WIDTH OF THE SWITCH GEAR. MUST BE LEVEL TO PROVIDE SAFETY AND A PLATFORM FREE OF A TRIP HAZARD WHICH THE CURB PRESENTS THIS SITUATION MUST BE RESOLVED PRIOR TO ANY FINALS OR TEMP C OF O'S
01/18/2007 ELECTRIC - CONSTRUCTION POWER RMAJUTA Approved IVRS - Inspection :*
01/18/2007 ELECTRIC - CONSTRUCTION POWER RMAJUTA Approved IVRS - Inspection :*
01/18/2007 ELECTRIC - CABLE DROP RMAJUTA Approved IVRS - Inspection :*
02/22/2007 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
OK FOR FINAL
AIR BALANCE QUANTITIES ARE OK
TESTED DUCT SMOKE DETECTORS
03/05/2007 PLUMBING - FINAL RRICH Approved IVRS - Inspection :*
03/08/2007 ELECTRIC - FINAL RMAJUTA Approved IVRS - Inspection :*
PLANS HAVE BEEN REVISED TO EXCLUDE
1. COMPRESSOR & ITS FEED
2. X-RAY & ITS FEED
3. CATSCAN & ITS FEED

ALSO, OMIT FUTURE 1000A SERVICE TO FEED EQUIPMENT 1-3
03/21/2007 FIRE - FINAL CSCHULTZ Approved
03/21/2007 FIRE SPKLR - FINAL CSCHULTZ Approved
05/25/2007 ENGINEERING - FINAL DROBERTS Approved ALL PREVIOUSLY NOTED ITEMS HAVE BEEN COMPLETED EXCEPT THE REMOVAL OF THE DUMPSTER. THIS HAS BEEN RELOCATED TO THE PARKING AREA ALONG THE WEST SIDE OF THE SITE AND WILL BE REMOVED NEXT WEEK.
05/25/2007 ENGINEERING - FINAL JFEMLING Approved 1) FINISH STRIPING FOR ADA ROUTE
2) REMOVE DUPSTER FROM PARKING LOT
3) REMOVE DIRT AND CONCRETE DEBRIS FROM DRIVEWAY AILES
BILL POTTER ADVISED OF THE MINOR WORK THAT NEEDS TO BE COMPLETED PRIOR TO FINAL RELEASE.
05/25/2007 BUILDING - FINAL GDABBS Approved IVRS - Inspection :*
06/13/2007 RIGHT OF WAY - FINAL SDAMRON Approved PER EMAIL
06/28/2007 PERMIT FINALED JYBARRA Approved
06/28/2007 SIGN - FINAL JYBARRA Approved