Permit: T05CM05829

Parcel: 14118001H


Addresses:

8290 S HOUGHTON RD


Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T05CM05829

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
01/18/2007 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
01/18/2007 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
NOTE: SECTION 110-26A NEC 2002 REQUIRES A DEPTH OF 3' IN FRONT OF THE SERVICE SWITCH GEAR, THIS AREA IS FOR THE SAFETY OF MAINTENANCE AND EXAMINATION OF THE SWITCH GEAR. THIS AREA HAS TO BE THE WIDTH OF THE SWITCH GEAR. MUST BE LEVEL TO PROVIDE SAFETY AND A PLATFORM FREE OF A TRIP HAZARD WHICH THE CURB PRESENTS THIS SITUATION MUST BE RESOLVED PRIOR TO ANY FINALS OR TEMP C OF O'S
01/17/2007 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1. NEED LETTER FROM EE ON CHANGE SERVICE FEEDER AL FROM CU
2. NEED BOND FOR TEC
3. NEED LETTER FROM CONTRACTOR ON SWITCH GEAR TORQUE PER MANUFACTURES REQUIREMENTS.