Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2007 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* | |
| 01/18/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* NOTE: SECTION 110-26A NEC 2002 REQUIRES A DEPTH OF 3' IN FRONT OF THE SERVICE SWITCH GEAR, THIS AREA IS FOR THE SAFETY OF MAINTENANCE AND EXAMINATION OF THE SWITCH GEAR. THIS AREA HAS TO BE THE WIDTH OF THE SWITCH GEAR. MUST BE LEVEL TO PROVIDE SAFETY AND A PLATFORM FREE OF A TRIP HAZARD WHICH THE CURB PRESENTS THIS SITUATION MUST BE RESOLVED PRIOR TO ANY FINALS OR TEMP C OF O'S |
|
| 01/17/2007 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1. NEED LETTER FROM EE ON CHANGE SERVICE FEEDER AL FROM CU 2. NEED BOND FOR TEC 3. NEED LETTER FROM CONTRACTOR ON SWITCH GEAR TORQUE PER MANUFACTURES REQUIREMENTS. |