Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM05829

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/17/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
1. PNL A OK
2. PNL B OK
3. PNL AC OK
4. PNL C OK
5. WATER LINE & SPRINKLER BOND'S OK
6. SERVICE ENTRANCE CONDUCTORS ON PLANS 500 MCM COPPER, 750 MCM ALUM PULLED IN - GET EE'S OK
7. LETTER ON TORQUE PER COMPANY REQUIRED
8. POWER BOND REQUIRED
9. POLE LIGHTS OK (6)
12/26/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. FINISH ATTACHING BOTTOM ENDS FOR VDV CABELING 300.11
2. MAINTAIN CLEARANCES FOR DISCONNECT ABOVE CEILING.
3. SUPPORT CABLES UPON EXITING CABLE TRAY 392.6
4. PLEASE VERIFY CABLE TRAY BOND PER 392.6 & 7

OK 2X2 FIXTURES
12/19/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. 2X2 FIXTURES REQUIRED TO HAVE APPROVED CLIP OR FITTING TO ATTACH & SECURE IT TO T-BAR 410.16 NEC
LOBBY AREA
2. OK TO COVER ALL 2X4 CEILING FIXTURE AREA
BACK AREA
09/19/2006 ELECTRIC - ABOVE CEILING Partial Approval HARDLIDS ABOVE COUNTERS