Permit: T05CM05829

Parcel: 14118001H


Addresses:

8290 S HOUGHTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05829

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/08/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
PLANS HAVE BEEN REVISED TO EXCLUDE
1. COMPRESSOR & ITS FEED
2. X-RAY & ITS FEED
3. CATSCAN & ITS FEED

ALSO, OMIT FUTURE 1000A SERVICE TO FEED EQUIPMENT 1-3
03/05/2007 ELECTRIC - FINAL Partial Approval 1. SCREW DOWN CABLES IN SWITCH GEAR
2. ROOF OK
3. MISSING FIXTURES ON NORTH SIDE WALL
4. LETTER ON OMISSION ITEM #9
02/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TYPE ORIGINAL SCHEDULES IN PANELS NO PLAN COPIES
2. INSTALL K-O SEALS IN FIRE ALARM CONTROLLER AT ENTRY
3. FIX LOCK MECHANISM ON PNL B, ALSO DO PERMANENT SCHEDULES FOR PNL B & AC
4. RECEPTACLE COVERS MISSING AT FRONT SOUTHERN RECEP AREA UNDER DESK
5. PERMANENT PLAQUES ON SWITCH GEAR TO ID DISCONNECTS
6. NEED LEVEL LANDING IN FRONT OF SW GEAR 36" OUT IN FRONT.
7. CHECK EM LIGHTS IN ROOMS 5110 NOT IN, S109 NOT WORKING, CORRIDOR R101 EM NOT IN.
8. NEED ACCESS TO ROOF TO CK AC EQUIPMENT, BEFORE INSPECTION HAVE ELECTRICIAN VERIFY DISCONNECT FOR EQUIPMENT HAVE A PERMANENT ID INDICATING PANEL AND CIRCUIT #'S
9. WHAT WILL HAPPEN TO 2ND SERVICE ON SHEET E-5
WILL ALL THIS BE OMITTED IF SO PROVIDE A LETTER OF OMISSION.