Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM05829
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* REVISED APPROVED PLAN ON SITE |
|
09/20/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - WATER TEST WASTE & VENT THRU ROOF OK SHALL REDLINE VENTS THRU ROOF. - WATER PIPING IN WALL OK SHALL PROVIDE REVISED APPROVED PLAN FOR OVERHEAD WATER DISTRIBUTION FOR SIZING. |
|
09/19/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 3" ROOF DRAIN & OVERFLOW RAIN DRAIN WATER TEST OK |
|
05/17/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNDERGROUND WASTE & VENT FROM HCS INTO BUILDING THRU BUILDING PER REDLINE ON SITE DUE TO T.I. & SHELL PLAN NOT WORK TOGETHER. 1. NEED FULL SIZE IN LINE CLEANOUT ON 4" BUILDING DRAIN ON WEST RUN, NEED INSTALL OF P-TRAPS FOR SHOWER & FLOOR DRAIN, NEED 3" FULL SIZE UPPER TERMINAL CLEANOUTS OF BRANCHES OVER 5' FROM TRUNK DRAIN. 2. PROVIDE SIZES OF DRAINS ON REDLINE. |