Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
DUPLEX NEW
Apply Date:
08/19/2005
Applicant:
J 3 CO A CONSTRUCTION AND CONSULTING COMPANY L L
Description:
NEW DUPLEX
Contractors:
  • J 3 CO A CONSTRUCTION AND CONSULTING COMPANY L L

Permit Reviews

Permit Number - T05CM04341
Permit Status: Final
Permit Description: NEW DUPLEX
Start Date Submittal Complete Date Status  
08/19/2005 PLANS OK TO SUBMIT - RES 08/19/2005 COMPLETED Review Details
08/19/2005 RESIDENTIAL BLDG/ZONING/ENGINE/WWM 09/23/2005 COMPLETED Review Details
10/18/2005 RESUBMITTAL 11/08/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM04341
Permit Status: Final
Permit Description: NEW DUPLEX
Total Outstanding Activity Conditions - 1
Date Name
08/19/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T05CM04341
Permit Description: NEW DUPLEX
Total Completed Inspections - 22
Date Description Inspector Results Comments
11/17/2005 PLUMBING - SEWER HCS CONNECT RRICH Approved IVRS - Inspection :*NEED TO VIEW PIPE WRAPS PRIOR TO CONCRETE POUR
11/29/2005 ELECTRIC - UFER CCLEMENS Approved IVRS - Inspection :*
12/01/2005 BUILDING PRE-SLAB LHANLY Approved IVRS - Inspection :*
12/01/2005 EXCAVATION/LAYOUT REBAR & ZON LHANLY Approved IVRS - Inspection :*
12/02/2005 PLUMBING - ROUGH, SOIL TRINIVJR Approved IVRS - Inspection :*
1) ALL DWV RISERS HAVE BEEN WRAPPED
03/01/2006 U VALUE FOR WINDOW AQUIROZ Approved IVRS - Inspection :*
03/01/2006 EXT METAL CLIPS/EXT SHEATHING AQUIROZ Approved IVRS - Inspection :*
03/09/2006 ROOF NAILING AQUIROZ Approved IVRS - Inspection :*
03/22/2006 STUCCO MESH AQUIROZ Approved IVRS - Inspection :*
03/31/2006 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection :*
1. CANNOT HAVE GFI RECEPTACLE BELOW SERVICE ON 200 AMP MAIN
2. GROUND WIRE FROM GROUND RODS TO LAND AT NEUTRAL TO GROUND SERVICE.
04/02/2006 FRAMING AQUIROZ Approved IVRS - Inspection :*
04/03/2006 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
1. CORRECTIONS MADE OK
OK TO COVER ALL AREAS
CLOSET FLANGES OK
04/13/2006 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :*
04/21/2006 ELECTRIC - CABLE DROP CCLEMENS Approved IVRS - Inspection :*
1) OK TO COVER DITCH FOR SERVICE LATARELL
2) INSTALL WARNING RIBBON MINIMUM 12" ABOVE SERVICE RACEWAY
04/24/2006 TEP CLEARANCE - AM JWEATHER Approved ECO CLEARED FOR UNITS #1 & #2 PER C. CLEMENS
05/08/2006 SHEET ROCK NAILING JBURGE Approved IVRS - Inspection :*
12/22/2006 BUILDING - FINAL JBURGE Approved IVRS - Inspection :*
12/28/2006 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) MARK UNIT DATA PLATE WITH THE PROPER AUX. HEAT KITCHEN INSTALLED AND FUSE ACCORDINGLY
2) DO NOT USE WHITE WIRE TO POWER A/C UNIT
3) PROVIDE CONDUIT FOR LOW VOLTAGE WIRES
4) REDWOOD SLEEPERS MUST BE FLAT ON THE ROOF AND SPAN THE JOISTS
5) PAINT EXPOSED PVC WITH LATEX PAINT
6) PROVIDE SCREEN IN ALL EXHAUST FAN T-TOPS
12/28/2006 PLUMBING - GAS PRESSURE TEST RRICH Approved IVRS - Inspection :*
12/29/2006 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :*
1) UNITS LOCKED
12/29/2006 PLUMBING - FINAL RRICH Approved IVRS - Inspection :*
01/09/2007 PLUMBING - YARD WTR LINE/TEST RMYERS Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW