Permit: T05CM04341

Parcel: 11105291B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM04341

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/29/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) UNITS LOCKED
12/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) MOUNT WATER HEATER DISCONNECT SO IT IS ACCESSIBLE AND HAS PROPER WORKING CLEARANCE AND STRAP FLEX-NEC 110.26
2) SMOKE DETECTORS REQUIRE ARC FAULT PROTECTION-NEC 210.12
3) USE CONNECTOR FOR DISWASHER CORD INTO J-BOX-NEC 400.14
4) SECURE RANGE ANTI-TIP BRACKET TO FLOOR-NEC 110.3
5) CHECK THESE CORRECTIONS IN BOTH UNITS
12/22/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
WATER HTR DISCONNECT REQUIRED OR LOCKOUT AT CIRCUIT.