Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05CM04341
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
12/28/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MARK UNIT DATA PLATE WITH THE PROPER AUX. HEAT KITCHEN INSTALLED AND FUSE ACCORDINGLY 2) DO NOT USE WHITE WIRE TO POWER A/C UNIT 3) PROVIDE CONDUIT FOR LOW VOLTAGE WIRES 4) REDWOOD SLEEPERS MUST BE FLAT ON THE ROOF AND SPAN THE JOISTS 5) PAINT EXPOSED PVC WITH LATEX PAINT 6) PROVIDE SCREEN IN ALL EXHAUST FAN T-TOPS |
|
12/22/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* PROVIDE ACCESS TO UPPER ROOF |