Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T05CM04341
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/21/2006 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* 1) OK TO COVER DITCH FOR SERVICE LATARELL 2) INSTALL WARNING RIBBON MINIMUM 12" ABOVE SERVICE RACEWAY |
|
04/13/2006 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* GROUNDING ELECTRODE CONDUCTOR STOLEN |
|
03/31/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
03/27/2006 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1. TERMINATE ALL STRANDS OF CONDUCTOR. 2. TEMP POWER TO BE OUTSIDE BUILDING 3. PROTECT NM CABLES AT STUDS 300.4 4. OUTSIDE GFI'S NOT TO BE ON BATHROOM CIRCUIT 5. TIGHTEN LOOSE FITTINGS AT PANEL 6. USE APPROVED PVC FOR SLEEVING 7. FINISH PREVIOUS ITEMS |
|
03/22/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The service is not per code.| 210* 1. INSTALL PERMANENT ADDRESS LABELS ON SERVICE 2. TIGHTEN BONDING JUMPER SCREWS TO ENCLOSURE 3. TIGHTEN BOND CONNECTIONS TO RISER 4. INSTALL GROUNDING ELECTRODE TO SERVICE 5. NEED EXTERIOR RECEPTACLES AT THE FRONT AND BACK OF EACH UNIT - NEC 210.52 (E) 6. USE PROPER CRIMP TOOL FOR ALL CRIMP SLEEVES NEC 110.3 (B) 7. HAVE OVERFILLED BOXES NEC 314.16 8. PROPERLY GROUND ALL METAL BOXES (TIGHTEN GROUND SCREWS) 9. GROUNDS AND NEUTRALS IN SUB PANELS NEED TO BE SEPARATED AND ENCLOSURES GROUNDED. 10. SER ENTERING SUB-PANELS NEED CONNECTORS AND BUSHINGS NEC 300.4 (F) 11. PROVIDE PROPER FIRE STOPPING FOR PENETRATIONS THROUGH RATED WALLS. 12. NEED BATH GFI WITHIN 3' OF SINK NEC 210.52 (D) |