Permit: T05CM04341

Parcel: 11105291B

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T05CM04341

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
04/21/2006 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
1) OK TO COVER DITCH FOR SERVICE LATARELL
2) INSTALL WARNING RIBBON MINIMUM 12" ABOVE SERVICE RACEWAY
04/13/2006 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
GROUNDING ELECTRODE CONDUCTOR STOLEN
03/31/2006 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/27/2006 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1. TERMINATE ALL STRANDS OF CONDUCTOR.
2. TEMP POWER TO BE OUTSIDE BUILDING
3. PROTECT NM CABLES AT STUDS 300.4
4. OUTSIDE GFI'S NOT TO BE ON BATHROOM CIRCUIT
5. TIGHTEN LOOSE FITTINGS AT PANEL
6. USE APPROVED PVC FOR SLEEVING
7. FINISH PREVIOUS ITEMS
03/22/2006 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The service is not per code.| 210*
1. INSTALL PERMANENT ADDRESS LABELS ON SERVICE
2. TIGHTEN BONDING JUMPER SCREWS TO ENCLOSURE
3. TIGHTEN BOND CONNECTIONS TO RISER
4. INSTALL GROUNDING ELECTRODE TO SERVICE
5. NEED EXTERIOR RECEPTACLES AT THE FRONT AND BACK OF EACH UNIT - NEC 210.52 (E)
6. USE PROPER CRIMP TOOL FOR ALL CRIMP SLEEVES NEC 110.3 (B)
7. HAVE OVERFILLED BOXES NEC 314.16
8. PROPERLY GROUND ALL METAL BOXES (TIGHTEN GROUND SCREWS)
9. GROUNDS AND NEUTRALS IN SUB PANELS NEED TO BE SEPARATED AND ENCLOSURES GROUNDED.
10. SER ENTERING SUB-PANELS NEED CONNECTORS AND BUSHINGS NEC 300.4 (F)
11. PROVIDE PROPER FIRE STOPPING FOR PENETRATIONS THROUGH RATED WALLS.
12. NEED BATH GFI WITHIN 3' OF SINK NEC 210.52 (D)