Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM04341
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1. CORRECTIONS MADE OK OK TO COVER ALL AREAS CLOSET FLANGES OK |
|
03/27/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NO READY |
|
03/23/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* TRAP ARM MAY NOT CHANGE SIZE TRAP AND TRAP ARM TO BE THE SAME SIZE TRAP MAY BE ONLY ONE SIZE LARGER THAN TAILPIECE TO WHICH IT IS CONNECTED. TRAP ARM TO BE 2X PIPE DIAMETER IN LENGTH. STAND PIPE TO BE 18"-30" STAND PIPE TRAP TO BE ROUGHED IN NO LESS THAN 6" AFF AND NO MORE THAN 18" AFF. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES. SUPPORT SHALL NOT BE FROM THE FITTING NO MORE THAN 4' BETWEEN ABS HAS A FEW MINOR LEAKS THAT NEED TO BE FIXED. CLOSET FLANGES TO BE SUPPORTED SCREWS SHALL BE STAINLESS STEEL OR BRASS. |