Permit: T02CM02284
Permit Details
Apply Date:
05/07/2002
Applicant:
POSTER, CHARLES MARCUS
Description:
NEW:COMMUNITY CENTER TWO WINGS WITH LOBBY AND COURTYARD SEPARATING THEM. MULTI-USE/ CLASSROOM WING ADMIN/WEIGHT/MUSIC/CERAMICS WING
Architects:
- POSTER, CHARLES MARCUS
Contractors:
- DIVERSIFIED DESIGN AND CONSTRUCT
Permit Reviews
Permit Number - T02CM02284
Permit Status: C of o
Permit Description: NEW:COMMUNITY CENTER TWO WINGS WITH LOBBY AND COURTYARD SEPARATING THEM. MULTI-USE/ CLASSROOM WING ADMIN/WEIGHT/MUSIC/CERAMICS WING
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
02/19/2004 | REVISION | 03/11/2004 | COMPLETED |
05/07/2002 | COMMERCIAL NEW | 07/12/2002 | COMPLETED |
05/07/2002 | SITE | 07/12/2002 | COMPLETED |
07/12/2002 | RESUBMITTAL | 08/27/2002 | COMPLETED |
07/12/2002 | RESUBMITTAL | 08/27/2002 | COMPLETED |
08/27/2002 | RESUBMITTAL | 09/02/2003 | COMPLETED |
08/27/2002 | RESUBMITTAL - SITE | 09/02/2003 | COMPLETED |
12/29/2003 | RESUBMITTAL | 12/30/2003 | COMPLETED |
12/30/2003 | REVISION | 01/22/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T02CM02284
Permit Status: C of o
Permit Description: NEW:COMMUNITY CENTER TWO WINGS WITH LOBBY AND COURTYARD SEPARATING THEM. MULTI-USE/ CLASSROOM WING ADMIN/WEIGHT/MUSIC/CERAMICS WING
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
05/07/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T02CM02284
Permit Description: NEW:COMMUNITY CENTER TWO WINGS WITH LOBBY AND COURTYARD SEPARATING THEM. MULTI-USE/ CLASSROOM WING ADMIN/WEIGHT/MUSIC/CERAMICS WING
Total Completed Inspections - 41
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2003 | ELECTRIC - CONSTRUCTION POWER | JORTA | Approved | IVRS - Inspection 0000* SENT TO TEP 09/16/2003 9:15A.M. |
10/16/2003 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection 0000* |
10/16/2003 | PLUMBING - ROUGH, SOIL | RRICH | Approved | IVRS - Inspection 0000*/ 1) WASTE AND VENT (SOIL) UNDERGROUND WATER TEST OK FOR NORTH BLDG. |
10/27/2003 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | IVRS - Inspection 0000*/ 1) 2 ground rods at sw gear 3/0 copper. 2) remaining underground for bldg south half, including electric room, telecom room and associated feeders. |
10/30/2003 | STEM WALL/RETAINING WALL | LHANLY | Approved | IVRS - Inspection 0000* |
11/06/2003 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection 0000*/ 2-1/2 T/K H2O FROM MULTI USE ROOM TO RESTROOMS UNDERGROUND 100 PSI AIR TEST OK. |
11/20/2003 | BUILDING PRE-SLAB | LHANLY | Approved | IVRS - Inspection 0000* |
11/20/2003 | EXCAVATION/LAYOUT REBAR & ZON | LHANLY | Approved | IVRS - Inspection 0000* |
12/09/2003 | ELECTRIC - UFER | RMAJUTA | Approved | IVRS - Inspection 0000* |
12/18/2003 | ELECTRIC - INTERMEDIATE | JORTA | Approved | IVRS - Inspection 0000*/ PLUS UNDERGROUND FOR QWEST COMPLETE. |
12/30/2003 | PLUMBING - SEWER HCS CONNECT | RRICH | Approved | IVRS - Inspection 0000*/ WTR TEST ON 4" BLDG SEWER FROM WYE TO BOTH BLDG HCS CONNECTIONS APPROVED. |
01/05/2004 | EXT METAL CLIPS/EXT SHEATHING | LHANLY | Approved | IVRS - Inspection 0000* |
01/13/2004 | PLUMBING - YARD WTR LINE/TEST | RRICH | Approved | IVRS - Inspection 0000*/ 3" FROM METER TO BLD SERVICE CONNECTION - 50 PSI AIR TEST OK. WILL NEED TO SEE BACKFLOW PROTECTION AND CERTIFICATION. |
02/04/2004 | ELECTRIC - ABOVE CEILING | JORTA | Approved | IVRS - Inspection 0000*/ 1) EXTERIOR SOFFITS AND HARD CEILINGS APPROVED |
02/10/2004 | SHEET ROCK NAILING | LHANLY | Approved | IVRS - Inspection 0000* INTERIOR COMPLETE |
02/10/2004 | FRAMING | LHANLY | Approved | IVRS - Inspection 0000* |
02/10/2004 | ROOF NAILING | LHANLY | Approved | IVRS - Inspection 0000* |
02/12/2004 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
02/18/2004 | STUCCO MESH | LHANLY | Approved | IVRS - Inspection 0000* |
02/18/2004 | REINFORCED MASONRY PRE-GROUT | LHANLY | Approved | IVRS - Inspection 0000* |
03/25/2004 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
03/25/2004 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
04/01/2004 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection 0000*/ INSPECTED SUSPENDED ROUGH DUCT. FINISH FLEX AND DIFFUSERS. INSPECTED 2ND LAYER FIRE WRAP. WRAP MUST EXTEND ALL THE WAY TO TOP OF GREASE DUCT. PARTICLE BOARD IN PLENIUM CEILING MUST BE COVERED WITH APPROVED COVERING. |
04/08/2004 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
04/13/2004 | PLUMBING - GAS PRESSURE TEST | RRICH | Approved | IVRS - Inspection 0000* |
04/29/2004 | RIGHT OF WAY - FINAL | DLEE | Approved | |
04/29/2004 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
04/29/2004 | OUTDOOR LIGHTING FINAL | JORTA | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
05/10/2004 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection : See detailed listing on site.| 999*/ OK FOR FINAL C OF O. |
05/10/2004 | MECHANICAL - HOODS | JMILITEL | Approved | |
05/10/2004 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | |
05/10/2004 | NPPO - FINAL | ACONNOR | Approved | |
05/27/2004 | PLUMBING - PROGRESS | RRICH | Approved | IVRS - Inspection :* |
05/27/2004 | PLUMBING - ABOVE CEILING | RRICH | Approved | IVRS - Inspection :* |
06/16/2004 | FIRE - FINAL | LLAKEY | Approved | |
06/16/2004 | FIRE - KITCHEN EXH HOOD FINAL | LLAKEY | Approved | |
08/18/2004 | ELECTRIC - FINAL | JORTA | Approved | IVRS - Inspection :*/APPROVED |
09/21/2004 | BUILDING - FINAL | LHANLY | Approved | IVRS - Inspection :* |
09/21/2004 | BUILDING ABOVE CEILING | LHANLY | Approved | IVRS - Inspection :* |
09/21/2004 | ENGINEERING - FINAL | DROBERTS | Approved | |
10/13/2004 | PERMIT FINALED | TACHONG | Approved |