Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
Permit Number - T02CM02284
Inspection Description - ELECTRIC - CONSTRUCTION POWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2003 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection 0000* SENT TO TEP 09/16/2003 9:15A.M. |
|
09/11/2003 | ELECTRIC - CONSTRUCTION POWER | Denied | IVRS - Inspection 0210*/ INSTALL GROUND BUSH. AND BND JUMPER AT BOTH SIDES OF OFFSET NIPPLE. NEED NEUTRAL TO MAIN DISCONNECT. BRING #4 GROUND UP AND ATTACHED TO CONDUIT OR 4X4. PROVIDE AND COMPLETE A LOAD OR G.F.C.I. RECALL INSPECTION. |