Permit: T02CM02284

Parcel: 13101002H


Addresses:

5000 E 29TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Permit Number - T02CM02284

Inspection Description - ELECTRIC - CONSTRUCTION POWER

Inspection Status - Approved

Date Description Inspector Results Comments
09/15/2003 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection 0000*
SENT TO TEP 09/16/2003 9:15A.M.
09/11/2003 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection 0210*/ INSTALL GROUND BUSH. AND BND JUMPER AT BOTH SIDES OF OFFSET NIPPLE. NEED NEUTRAL TO MAIN DISCONNECT. BRING #4 GROUND UP AND ATTACHED TO CONDUIT OR 4X4. PROVIDE AND COMPLETE A LOAD OR G.F.C.I. RECALL INSPECTION.