Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM02284
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/18/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/APPROVED | |
05/18/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ DATA LABELS HAVE BEEN REPLACED WITH A MODIFIED VERSION. NEED TO CONSULT WITH THE E-2 INSPECTOR CONCERNING THE VALIDITY OF SUCH ACTION WITHOUT THE DIRECT INVOLVEMENT OF THE LISTING AGENCY (U.L.) | |
05/10/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ NEED LETTER OF VERIFICATION ON OK TO USE SWITCHGEAR AS SECONDARY SERVICE FOR STRUCTURAL FROM EE. | |
05/02/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SEE COMMENTS IN REFERENCE TO SWITCH BOARD LISTING. INSPECTION OF 4/29/04 |
|
04/29/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SWITCH BOARD 800 AMP IS LISTED FOR USE AS SERVICE EQUIPMENT ONLY |
|
04/13/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ SPRINKLER PIPE ABOVE 800 ANP SES IN VIOLATION OF FORIEGN EQUIPMENT ABOVE. CORD ISSUES WITH ONE LINE TO BE CONFIRMED. NEED CLARIFICATION. | |
03/17/2004 | ELECTRIC - FINAL | Not ready for Inspection | OK FOUR - 4" CONDUITS TO NEW UTILITY TU APPROVED. | |
03/17/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) OK TO ENERGIZE NEW SERVICE ENTRANCE, TO ENERGIZE PARK AREA LIGHTING AND PARK POOL SERVICE |