Permit: T02CM02284

Parcel: 13101002H


Addresses:

5000 E 29TH ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02CM02284

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/10/2004 MECHANICAL - FINAL Approved IVRS - Inspection :
See detailed listing on site.| 999*/ OK FOR FINAL C OF O.
05/07/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :
See detailed listing on site.| 999* BREAKER FOR CONDENSING UNTI TOO SMALL AT 15AMP. 20 AMP IS MIN. RECALL FOR FINAL OR HAVE ELC INSPEC. CHECK ON NEXT VISIT.
04/30/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/ 1) CU-1 CIRCUIT BREAKER TOO SMALL AND FUSES TO LARGE. SEE DATA PLATE ON CONDENSOR 2) NEED TO SEE KITCHEN EXHAUST INTERLOCKED 3) NEED TO TEST DUCT SMOKE DETECTORS. PROVIDE INSTALL INSTRUCTIONS