Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection : See detailed listing on site.| 999*/ OK FOR FINAL C OF O. |
|
| 05/07/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection : See detailed listing on site.| 999* BREAKER FOR CONDENSING UNTI TOO SMALL AT 15AMP. 20 AMP IS MIN. RECALL FOR FINAL OR HAVE ELC INSPEC. CHECK ON NEXT VISIT. |
|
| 04/30/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*/ 1) CU-1 CIRCUIT BREAKER TOO SMALL AND FUSES TO LARGE. SEE DATA PLATE ON CONDENSOR 2) NEED TO SEE KITCHEN EXHAUST INTERLOCKED 3) NEED TO TEST DUCT SMOKE DETECTORS. PROVIDE INSTALL INSTRUCTIONS |