Permit: TC-COM-1125-02118
Permit Details
Apply Date:
11/18/2025
Applicant:
Fernando Govin Cossio
Description:
40TH ST REMODEL, New Certificate of Occupancy for New Sober Living Facility (per applicant Michael Hernandez 12/11/25 12:36pm)
Permit Reviews
Permit Number - TC-COM-1125-02118
Permit Status: Complete
Permit Description: 40TH ST REMODEL, New Certificate of Occupancy for New Sober Living Facility (per applicant Michael Hernandez 12/11/25 12:36pm)
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 11/24/2025 | COMMERCIAL REVIEW - FULL v.1 | 12/17/2025 | REQUIRES RESUBMIT |
| 04/09/2026 | ADMINISTRATIVE v.1 | 04/09/2026 | REQUIRES RESUBMIT |
| 04/03/2026 | COMMERCIAL REVIEW - FULL v.3 | 04/07/2026 | APPROVED |
| 07/17/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 07/23/2026 | APPROVED |
| 03/04/2026 | COMMERCIAL REVIEW - FULL v.2 | 03/26/2026 | REQUIRES RESUBMIT |
Conditions
Permit Number - TC-COM-1125-02118
Permit Status: Complete
Permit Description: 40TH ST REMODEL, New Certificate of Occupancy for New Sober Living Facility (per applicant Michael Hernandez 12/11/25 12:36pm)
| Date | Description | Comments |
|---|---|---|
| 11/24/2025 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 12/11/2025 | An Operator's License must be applied for with the State, the absence of this license shall void this building permit. | |
| 11/24/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. | |
| 12/15/2025 | WATER STERILIZATION REPORT IS REQUIRED. |
Outstanding Inspections
Permit Status: Complete
Permit Number: TC-COM-1125-02118
Permite Description: 40TH ST REMODEL, New Certificate of Occupancy for New Sober Living Facility (per applicant Michael Hernandez 12/11/25 12:36pm)
Total Outstanding Inspections - 4
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COT - FCON - Fire - Final | N/A | Not Ready | ||
| 07/14/2026 | COT - LCME - Mechanical Final | N/A | Re-inspection required | 7-14-26: side grab bar must be a minimum of 42" in length, grab bar must be installed no further than 12" from end of wall, lower grab bar height to 36" aff, shower seat must be installed 17" to 19" max height, install knee guards at lavatory, mirror must be lowered to 40" to the reflective surface, toilet paper height is 17-19" aff , electrical panel schedule not per approved plans, HVAC breaker must be a 60 amp, restroom breaker calls for a 20 amp breaker vs. a 15 amp breaker, complete stucco at back door, install vacuum breakers at hose bibs, a GFCI receptacle at laundry room is required. Missing tracer wire at tie-in. Stopped inspection-additional items may be noted. |
| 07/14/2026 | COT - LCBU - Building Final | N/A | Re-inspection required | 7-14-26: side grab bar must be a minimum of 42" in length, grab bar must be installed no further than 12" from end of wall, lower grab bar height to 36" aff, shower seat must be installed 17" to 19" max height, install knee guards at lavatory, mirror must be lowered to 40" to the reflective surface, toilet paper height is 17-19" aff , electrical panel schedule not per approved plans, HVAC breaker must be a 60 amp, restroom breaker calls for a 20 amp breaker vs. a 15 amp breaker, complete stucco at back door, install vacuum breakers at hose bibs, a GFCI receptacle at laundry room is required. Stopped inspection-additional items may be noted. |
| 07/14/2026 | COT - LCEL - Electrical Final | N/A | Re-inspection required | 7-14-26: side grab bar must be a minimum of 42" in length, grab bar must be installed no further than 12" from end of wall, lower grab bar height to 36" aff, shower seat must be installed 17" to 19" max height, install knee guards at lavatory, mirror must be lowered to 40" to the reflective surface, toilet paper height is 17-19" aff , electrical panel schedule not per approved plans, HVAC breaker must be a 60 amp, restroom breaker calls for a 20 amp breaker vs. a 15 amp breaker, complete stucco at back door, install vacuum breakers at hose bibs, a GFCI receptacle at laundry room is required. Stopped inspection-additional items may be noted. |
Completed Inspections
Permit Status: Complete
Permit Number: TC-COM-1125-02118
Permit Description: 40TH ST REMODEL, New Certificate of Occupancy for New Sober Living Facility (per applicant Michael Hernandez 12/11/25 12:36pm)
Total Completed Inspections - 10
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2026 | COT - LCME - Mechanical Intermediate | Passed | 5-21-26: approved. | |
| 06/11/2026 | COT - LCPL - Plumbing Intermediate | Passed | 6-11-26: plumbing intermediates approved. | |
| 07/14/2026 | COT - LCBU - Framing | Passed | 7-14-26: approved. | |
| 07/14/2026 | COT - LCBU - Preslab | Passed | 7-14-26: approved. | |
| 07/21/2026 | COT - FCON - Fire - Final | Passed | ||
| 07/21/2026 | COT - LCME - Mechanical Final | Passed | 7-21-26: mechanical final approved. | |
| 07/21/2026 | COT - LCPL - Rough Soil | Passed | 7-21-26: tie in approved. Okay to backfill using shading materials. | |
| 07/21/2026 | COT - LCPL - Plumbing Final | Passed | 7-21-26: plumbing final approved. | |
| 07/23/2026 | COT - LCBU - Building Final | Passed | 7-23-26: Building final approved- Okay to apply for a C of O. | |
| 07/23/2026 | COT - LCEL - Electrical Final | Passed | 7-23-26: Electrical final approved. |