Inspection Status: Re-inspection required

Inspection History: COT - LCBU - Building Final 

Date Description Inspector Results Comments
07/14/2026 COT - LCBU - Building Final  Re-inspection required 7-14-26: side grab bar must be a minimum of 42" in length, grab bar must be installed no further than 12" from end of wall, lower grab bar height to 36" aff, shower seat must be installed 17" to 19" max height, install knee guards at lavatory, mirror must be lowered to 40" to the reflective surface, toilet paper height is 17-19" aff , electrical panel schedule not per approved plans, HVAC breaker must be a 60 amp, restroom breaker calls for a 20 amp breaker vs. a 15 amp breaker, complete stucco at back door, install vacuum breakers at hose bibs, a GFCI receptacle at laundry room is required. Stopped inspection-additional items may be noted.
07/21/2026 COT - LCBU - Building Final  Re-inspection required 7-21-26: extend condensation line on roof to 6" above grade, provide knockouts at panel together with an updated panel schedule, remove or cap existing light fixture under eave in front of home, add R3 insulation to hot copper line of water heater, replace flex pressure relieve valve at water heater with copper or CVPVC, add elbow to pressure relieve valve at front of home, break off screw tabs on all vacuum breakers.
07/23/2026 COT - LCBU - Building Final  Passed 7-23-26: Building final approved- Okay to apply for a C of O.