Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-COM-1125-02118

Parcel: 11903122B


Addresses:

731 W 40TH ST

Inspection Status: Re-inspection required

Inspection History: COT - LCME - Mechanical Final 

Date Description Inspector Results Comments
07/14/2026 COT - LCME - Mechanical Final  Re-inspection required 7-14-26: side grab bar must be a minimum of 42" in length, grab bar must be installed no further than 12" from end of wall, lower grab bar height to 36" aff, shower seat must be installed 17" to 19" max height, install knee guards at lavatory, mirror must be lowered to 40" to the reflective surface, toilet paper height is 17-19" aff , electrical panel schedule not per approved plans, HVAC breaker must be a 60 amp, restroom breaker calls for a 20 amp breaker vs. a 15 amp breaker, complete stucco at back door, install vacuum breakers at hose bibs, a GFCI receptacle at laundry room is required. Missing tracer wire at tie-in. Stopped inspection-additional items may be noted.
07/21/2026 COT - LCME - Mechanical Final  Passed 7-21-26: mechanical final approved.