Permit Details

Status:
Inspections
Type:
Commercial Building
Address:
20 E OCHOA ST
Address NEW:
20 E OCHOA ST
Apply Date:
09/19/2023
Applicant:
Brad Davis
Description:
THIS PROJECT IS A 7-STORY NEW CONSTRUCTION APARTMENT BUILDING. IT HAS 85 1-BEDROOM (585 NSF) DWELLING UNITS FOR THE ELDERLY. - BLDG A

Permit Reviews

Permit Number - TC-COM-0923-02239
Permit Status: Inspections
Permit Description: THIS PROJECT IS A 7-STORY NEW CONSTRUCTION APARTMENT BUILDING. IT HAS 85 1-BEDROOM (585 NSF) DWELLING UNITS FOR THE ELDERLY. - BLDG A
Start Date Submittal Complete Date Status  
08/19/2024 RESTAMP - COMMERCIAL v.1 08/21/2024 APPROVED Review Details
01/03/2024 COMMERCIAL REVIEW - FULL v.4 01/09/2024 APPROVED Review Details
01/09/2024 RESTAMP - COMMERCIAL v.1 01/10/2024 APPROVED Review Details
06/06/2024 COMMERCIAL REVIEW - FULL v.1 07/10/2024 REQUIRES RESUBMIT Review Details
10/27/2023 COMMERCIAL REVIEW - FULL v.2 12/08/2023 REQUIRES RESUBMIT Review Details
12/20/2023 COMMERCIAL REVIEW - FULL v.3 01/02/2024 REQUIRES RESUBMIT Review Details
08/13/2024 COMMERCIAL REVIEW - FULL v.2 08/19/2024 APPROVED Review Details
09/20/2023 COMMERCIAL REVIEW - FULL v.1 10/23/2023 REQUIRES RESUBMIT Review Details
09/03/2024 COMMERCIAL REVIEW - FULL REVISION v.1 09/30/2024 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0923-02239
Permit Status: Inspections
Permit Description: THIS PROJECT IS A 7-STORY NEW CONSTRUCTION APARTMENT BUILDING. IT HAS 85 1-BEDROOM (585 NSF) DWELLING UNITS FOR THE ELDERLY. - BLDG A
Total Outstanding Activity Conditions - 11
Date Name
01/09/2024 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
01/09/2024 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
01/09/2024 SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED.
01/09/2024 SPECIAL INSPECTION FOR FOUNDATION/EXCAVATION IS REQUIRED.
01/09/2024 SPECIAL INSPECTION FOR HIGH STRENGTH BOLTING IS REQUIRED.
01/09/2024 Masonry Inspection Report submittal review is required.
01/09/2024 SPECIAL INSPECTION FOR SPRAY-APPLIED FIRE PROOFING IS REQUIRED.
01/09/2024 SPECIAL INSPECTION FOR WELD REINF STEEL IS REQUIRED.
01/09/2024 SPECIAL INSPECTION FOR WELDING IS REQUIRED.
01/10/2024 WATER STERILIZATION REPORT IS REQUIRED.
11/14/2023 Prior to project being finalized applicant must provide recordation information for the new proposed aerial easement in the right of way along Jackson Street.

Conditions

Permit Number - TC-COM-0923-02239
Permit Status: Inspections
Permit Description: THIS PROJECT IS A 7-STORY NEW CONSTRUCTION APARTMENT BUILDING. IT HAS 85 1-BEDROOM (585 NSF) DWELLING UNITS FOR THE ELDERLY. - BLDG A
Date Description Comments
04/16/2024 Prior to Issuance: This project requires issuance of a Development Package (DP) permit prior to issuance of this permit. Prior to TCO/Final: This project requires full completion of a Development Package (DP) permit prior to Temporary C of O and/or final completion this permit.
09/20/2023 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-COM-0923-02239
Permite Description: THIS PROJECT IS A 7-STORY NEW CONSTRUCTION APARTMENT BUILDING. IT HAS 85 1-BEDROOM (585 NSF) DWELLING UNITS FOR THE ELDERLY. - BLDG A
Total Outstanding Inspections - 15
Last Inspection Date Description Inspector Results Comments
12/19/2024 COT - HCEL - Electrical Underground N/A Partial Pass Electric conduits for Secondary Electric System (5 at 4 “, 7 at 3”, 2,at 1 1/2”. Conduits to electric room, house panels, fire riser panel. Ok to cover progress areas.
03/24/2025 COT - HCBU - Excavation/Rebar/Zoning N/A Partial Pass 9/23/24: north stairwell at 32' Above finish floor reinforcement per plan ok to proceed, elevator CMU wall at 32' Above finish floor reinforcement per plan ok to proceed.
9/24/24: North stairwell at 36' above finish floor reinforcement per plan plan ok to proceed. Elevator CMU wall at 36' above finish floor reinforcement per plan ok to proceed.
9/25/24: North stairwell at 45' above finish floor reinforcement per plan ok to proceed.
9/30/24: North stairwell at 51' above finish floor, reinforcement per plan ok to proceed, Elevator CMU wall at 51' above finish floor, reinforcement per plan ok to proceed.
10/1/24: North stairwell at 57' above finish floor, reinforcement per plan ok to proceed, Elevator CMU wall at 57' above finish floor, reinforcement per plan ok to proceed.
10/2/24: North stairwell at 63' above finish floor, reinforcement per plan ok to proceed, Elevator CMU wall at 63' above finish floor, reinforcement per plan ok to proceed.
10/3/24:North stairwell at 69' above finish floor, reinforcement per plan ok to proceed, Elevator CMU wall at 69' above finish floor, reinforcement per plan ok to proceed.
10/4/24: North stairwell at 76' above finish floor, reinforcement per plan ok to proceed, Elevator CMU wall at 76' above finish floor, reinforcement per plan ok to proceed.
3/14/25: stair tower south reinforced per plan from 0'-4' ok to proceed with grout.
6/28/24: reinforcement per plan at elevator shaft slab. Ok to proceed.
7/2/24: Stair tower Mat slab @ Gridline C-E/11-13 ok to proceed.
3/14/25: stair tower south reinforced per plan from 0'-4' ok to proceed with grout.
318/25: 4th lift approved 24'-30'
3/24/25: reinforcement per approved at south west stair tower. Ok to proceed with concrete placement top out at 76'8".
06/12/2025 COT - HCEL - Electrical Progress N/A Partial Pass Level #1; in wall electric for rooms and corridors.
06/12/2025 COT - HCME - Mechanical Progress N/A Partial Pass Duct systems in room units and corridors.
07/21/2025 COT - HCME - Mechanical Above Ceiling N/A Partial Pass Level #1. room units. Ok to. over ceilings.
07/21/2025 COT - HCPL - Plumbing Above Ceiling N/A Partial Pass Level #1, room units. OK to cover ceilings.
07/21/2025 COT - HCEL - Electrical Above Ceiling N/A Partial Pass Level #1, room units. Ok to cover ceilings.
09/24/2025 COT - HCPL - Plumbing Progress N/A Partial Pass Level #4 Room units 401 - 413.
05/30/2025 COT - HCBU - Framing N/A Partial Pass Corridor walls and ceilings.
03/24/2025 COT - HCBU - Masonry Pregrout N/A Partial Pass 9/23/24: north stairwell at 32' Above finish floor reinforcement per plan ok to proceed, elevator CMU wall at 32' Above finish floor reinforcement per plan ok to proceed.
9/24/24: North stairwell at 36' above finish floor reinforcement per plan plan ok to proceed. Elevator CMU wall at 36' above finish floor reinforcement per plan ok to proceed.
9/25/24: North stairwell at 45' above finish floor reinforcement per plan ok to proceed.
9/30/24: North stairwell at 51' above finish floor, reinforcement per plan ok to proceed, Elevator CMU wall at 51' above finish floor, reinforcement per plan ok to proceed.
10/1/24: North stairwell at 57' above finish floor, reinforcement per plan ok to proceed, Elevator CMU wall at 57' above finish floor, reinforcement per plan ok to proceed.
10/2/24: North stairwell at 63' above finish floor, reinforcement per plan ok to proceed, Elevator CMU wall at 63' above finish floor, reinforcement per plan ok to proceed.
10/3/24:North stairwell at 69' above finish floor, reinforcement per plan ok to proceed, Elevator CMU wall at 69' above finish floor, reinforcement per plan ok to proceed.
10/4/24: North stairwell at 76' above finish floor, reinforcement per plan ok to proceed, Elevator CMU wall at 76' above finish floor, reinforcement per plan ok to proceed.
3/14/25: stair tower south reinforced per plan from 0'-4' ok to proceed with grout.
6/28/24: reinforcement per plan at elevator shaft slab. Ok to proceed.
7/2/24: Stair tower Mat slab @ Gridline C-E/11-13 ok to proceed.
3/14/25: stair tower south reinforced per plan from 0'-4' ok to proceed with grout.
318/25: 4th lift approved 24'-30'
3/24/25: reinforcement per approved at south west stair tower. Ok to proceed with concrete placement top out at 76'8".
12/12/2024 COT - HCEL - Grounding/Bonding N/A Partial Pass Ufer in place at area GL: 1 - 12/A - E.
11/26/2025 COT - BULD - SWG Clearance N/A Partial Pass 11/26/25: Gas pressure test approved. Pending tracer wire before backfill is approved
12/02/2025 COT - HCBU - Building Above Ceiling N/A Partial Pass 12/2/25: above ceiling approved 5th floor units only
06/23/2025 COT - HCBU - Building Progress N/A Partial Pass Level #3; corridor walls and ceilings framed. Ok to cover walls and ceilings. Level #4, Room units: hold downs are in place for all room units.
COT - HCBU - TCO N/A Requested

Completed Inspections

Permit Status: Inspections
Permit Number: TC-COM-0923-02239
Permit Description: THIS PROJECT IS A 7-STORY NEW CONSTRUCTION APARTMENT BUILDING. IT HAS 85 1-BEDROOM (585 NSF) DWELLING UNITS FOR THE ELDERLY. - BLDG A
Total Completed Inspections - 12
Date Description Inspector Results Comments
02/26/2025 PDSD Heavy Commercial Building Division Pre-Construction Meeting Passed
10/03/2025 COT - HCBU - Roof Nailing Passed
10/03/2025 COT - HCBU - Exterior Clips/Sheathing Passed
10/03/2025 COT - HCPL - Gas Pressure Test Passed
10/08/2025 COT - HCBU - Framing Passed
10/09/2025 COT - HCBU - Interior Shear Bracing Passed
10/09/2025 COT - HCBU - Masonry Pregrout Passed
10/09/2025 COT - HCBU - Preslab Passed
10/09/2025 COT - HCEL - Grounding/Bonding Passed
10/09/2025 COT - HCPL - Plumbing Roof Drains Passed
11/24/2025 BULD - Electrical Clearance Passed Request electric clearance for the,following equipment and placement of meters for each unit: SES1, SES2, Bus Way, HP-1, HP-2, HP-3, HP-4, HP-5, HP-6, HP-7, HP1A, MS1, MS2, MS3, MS4, MS5, MS6, MS7, METER BASES: 101, 102, 103, 104, 105, 106, 201, 202, 203, 204, 205, 206, 207, 208, 209, 210, 211, 212, 213, 301, 302, 303, 304, 305, 306, 307, 308, 309, 310, 311, 312, 313, 401, 402, 403, 404, 405, 406, 407, 408, 409, 410, 411, 412, 413, 501, 502, 503, 504, 505, 506, 507, 508, 509, 510, 511, 512, 513, 601, 602, 603, 604, 605, 606, 607, 608, 609, 610, 611, 612, 613, 701, 702, 703, 704, 705, 706, 707, 708, 709, 710, 711, 712, 713.
12/03/2025 COT - HCPL - Rough Soil Passed Lint trap installed. Ok to cover progress area.

Documents

File Name Document Type  
REVISED CONSTRUCTION PLANS 20 E OCHOA ST CD REV 4 8.21.24_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-20 E OCHOA ST CD REV 3 8.13.24_V2.PDF DOCUMENTS VIEW
FE APPROVAL 20 OCHOA BALCONY REVISION 6-12-24.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-4.DRAWINGS.20 E OCHOA ST CD REV 3 1.2.24_V4.PDF DOCUMENTS VIEW
CONS-4.DRAWINGS.20 E OCHOA ST CD REV 3 1.2.24_V4.PDF DOCUMENTS VIEW