Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: TC-COM-0725-01339
Permit Details
Status:
Inspections
Type:
Commercial Building
Address:
1660 W VALENCIA RD
Address NEW:
1660 W VALENCIA RD
Apply Date:
07/10/2025
Applicant:
Andrew Venne
Description:
Tenant Improvement
Permit Reviews
Permit Number - TC-COM-0725-01339
Permit Status: Inspections
Permit Description: Tenant Improvement
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/07/2025 | COMMERCIAL REVIEW - FULL v.2 | 08/07/2025 | REQUIRES RESUBMIT |
| 08/08/2025 | COMMERCIAL REVIEW - FULL v.3 | 08/19/2025 | APPROVED |
| 07/15/2025 | COMMERCIAL REVIEW - FULL v.1 | 08/06/2025 | REQUIRES RESUBMIT |
| 08/19/2025 | RESTAMP - COMMERCIAL v.1 | 08/19/2025 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-COM-0725-01339
Permit Status: Inspections
Permit Description: Tenant Improvement
Total Outstanding Activity Conditions - 2
| Date | Name |
|---|---|
| 08/06/2025 | AIR BALANCING REPORT IS REQUIRED. |
| 08/18/2025 | WATER STERILIZATION REPORT IS REQUIRED. |
Conditions
Permit Number - TC-COM-0725-01339
Permit Status: Inspections
Permit Description: Tenant Improvement
| Date | Description | Comments |
|---|---|---|
| 08/19/2025 | The Contractor you have added to your permit cannot be verified. Please contact staff to have the ROC number added to the account. | |
| 07/15/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-COM-0725-01339
Permite Description: Tenant Improvement
Total Outstanding Inspections - 8
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2025 | BULD - Electrical Clearance | N/A | Not Applicable | 12-19-25: not applicable. |
| 12/19/2025 | COT - LCBU - Building Final | N/A | Not Ready | 12-19-25: not ready. |
| 12/19/2025 | COT - LCEL - Electrical Final | N/A | Re-inspection required | 12-19-25: missing light and receptacle covers in office area, seal penetrations at demising wall and above ceiling at at office areas, re-label junction above above ceiling at east demising wall. Per NEC 300.11, you cannot use seismic wiring to support above ceiling junction boxes. Junction boxes must be independently, securely anchored from support from the structure above (joists/decking), with specific, distinguishable from "seismic bracing" wires. Panels-schedules and rooftop will be inspected at re-inspection. |
| 12/19/2025 | COT - LCME - Mechanical Final | N/A | Partial Pass | 12-19-25: install hand blower in restroom and Access to rooftop is required. Will check at building finals. |
| 12/19/2025 | COT - LCPL - Plumbing Final | N/A | Not Ready | 12-19-25: not ready. |
| 09/12/2025 | COT - LCBU - Framing | N/A | Partial Pass | 9/12/25: A small fur-out wall has been constructed over the plumbing in the Boy's restroom. Approved |
| 12/19/2025 | COT - LCPL - Plumbing Intermediate | N/A | Partial Pass | 12-19-25: install hand blower/ seal penetration on woman's restroom at lavatory. |
| 12/19/2025 | COT - LCEL - Electrical Intermediate | N/A | Re-inspection required | 12-19-25: missing light and receptacle covers in office area, seal penetrations at demising wall and above ceiling at at office areas, re-label junction above above ceiling at east demising wall. Per NEC 300.11, you cannot use seismic wiring to support above ceiling junction boxes. Junction boxes must be independently, securely anchored from support from the structure above (joists/decking), with specific, distinguishable from "seismic bracing" wires. |
Completed Inspections
Permit Status: Inspections
Permit Number: TC-COM-0725-01339
Permit Description: Tenant Improvement
Total Completed Inspections - 5
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2025 | COT - LCPL - Rough Soil | Passed | 9/5/25: Plumbing underground for (5)P-1 fixtures and (1)P-2 fixture per approved plans. Water test to a 10' stack which included DWV in wall rough-in for all plumbing fixtures. Ok To proceed with backfill | |
| 12/19/2025 | COT - LCPL - Plumbing Above Ceiling | Passed | 12-19-25: approved. | |
| 12/19/2025 | COT - LCBU - Framing | Passed | 12-19-25: approved. | |
| 01/05/2026 | COT - LCEL - Electrical Above Ceiling | Passed | ||
| 01/05/2026 | COT - LCME - Mechanical Above Ceiling | Passed |