Permit: TC-COM-0725-01339

Parcel: 13734001D


Addresses:

1660 W VALENCIA RD

Inspection Status: Re-inspection required

Inspection History: COT - LCEL - Electrical Final 

Date Description Inspector Results Comments
COT - LCEL - Electrical Final  Re-inspection required 3-24-26: install knee guards at restroom lavatories, adjust men's/girl's restroom doors to 5 pounds of pressure, install permanent labels at panels, seal all horizontal penetrations at firewall, label junction box near front office, remove exit sign above the northeast back classroom's door, install building address to where it's visible from parking lot.
03/27/2026 COT - LCEL - Electrical Final  Passed 3-27-26: electrical final approved.
12/19/2025 COT - LCEL - Electrical Final  Re-inspection required 12-19-25: missing light and receptacle covers in office area, seal penetrations at demising wall and above ceiling at at office areas, re-label junction above above ceiling at east demising wall. Per NEC 300.11, you cannot use seismic wiring to support above ceiling junction boxes. Junction boxes must be independently, securely anchored from support from the structure above (joists/decking), with specific, distinguishable from "seismic bracing" wires. Panels-schedules and rooftop will be inspected at re-inspection.