Inspection History: COT - LCEL - Electrical Above Ceiling 

Permit Number - TC-COM-0725-01339

Inspection Description - COT - LCEL - Electrical Above Ceiling 

Inspection Status - Passed

Date Description Inspector Results Comments
01/05/2026 COT - LCEL - Electrical Above Ceiling  Passed
12/19/2025 COT - LCEL - Electrical Above Ceiling  Re-inspection required 12-19-25: missing light and receptacle covers in office area, seal penetrations at demising wall and above ceiling at at office areas, re-label junction above above ceiling at east demising wall. Per NEC 300.11, you cannot use seismic wiring to support above ceiling junction boxes. Junction boxes must be independently, securely anchored from support from the structure above (joists/decking), with specific, distinguishable from "seismic bracing" wires.