Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Parcel: 13734001D


Addresses:

1660 W VALENCIA RD


Inspection Status: Partial Pass

Inspection History: COT - LCEL - Electrical Intermediate

Permit Number - TC-COM-0725-01339

Inspection Description - COT - LCEL - Electrical Intermediate

Inspection Status - Partial Pass

Date Description Inspector Results Comments
11/13/2025 COT - LCEL - Electrical Intermediate Partial Pass 11-13-25: partial pass-okay to continue with TI at progress areas.
11/24/2025 COT - LCEL - Electrical Intermediate Partial Pass 11-24-25: in wall electrical at south office space approved. Okay to continue with construction at progress areas.
12/19/2025 COT - LCEL - Electrical Intermediate Re-inspection required 12-19-25: missing light and receptacle covers in office area, seal penetrations at demising wall and above ceiling at at office areas, re-label junction above above ceiling at east demising wall. Per NEC 300.11, you cannot use seismic wiring to support above ceiling junction boxes. Junction boxes must be independently, securely anchored from support from the structure above (joists/decking), with specific, distinguishable from "seismic bracing" wires.