Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - LCEL - Electrical Intermediate
Permit Number - TC-COM-0725-01339
Inspection Description - COT - LCEL - Electrical Intermediate
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2025 | COT - LCEL - Electrical Intermediate | Partial Pass | 11-13-25: partial pass-okay to continue with TI at progress areas. | |
| 11/24/2025 | COT - LCEL - Electrical Intermediate | Partial Pass | 11-24-25: in wall electrical at south office space approved. Okay to continue with construction at progress areas. | |
| 12/19/2025 | COT - LCEL - Electrical Intermediate | Re-inspection required | 12-19-25: missing light and receptacle covers in office area, seal penetrations at demising wall and above ceiling at at office areas, re-label junction above above ceiling at east demising wall. Per NEC 300.11, you cannot use seismic wiring to support above ceiling junction boxes. Junction boxes must be independently, securely anchored from support from the structure above (joists/decking), with specific, distinguishable from "seismic bracing" wires. |