Permit: TC-COM-0725-01339

Parcel: 13734001D


Addresses:

1660 W VALENCIA RD

Inspection Status: Passed

Inspection History: COT - LCEL - Electrical Intermediate

Date Description Inspector Results Comments
03/24/2026 COT - LCEL - Electrical Intermediate Passed 3-24-26: approved.
11/13/2025 COT - LCEL - Electrical Intermediate Partial Pass 11-13-25: partial pass-okay to continue with TI at progress areas.
11/24/2025 COT - LCEL - Electrical Intermediate Partial Pass 11-24-25: in wall electrical at south office space approved. Okay to continue with construction at progress areas.
12/19/2025 COT - LCEL - Electrical Intermediate Re-inspection required 12-19-25: missing light and receptacle covers in office area, seal penetrations at demising wall and above ceiling at at office areas, re-label junction above above ceiling at east demising wall. Per NEC 300.11, you cannot use seismic wiring to support above ceiling junction boxes. Junction boxes must be independently, securely anchored from support from the structure above (joists/decking), with specific, distinguishable from "seismic bracing" wires.