Permit: TC-COM-0624-01123
Permit Details
Apply Date:
06/11/2024
Applicant:
Zoe Sadorf
Description:
Restricted Record - CoT Total renovation of 17 story Tucson House Building including replacement of mechanical and electrical systems and elevators. Complete update of parking and site areas.
Permit Reviews
Permit Number - TC-COM-0624-01123
Permit Status: In review
Permit Description: Restricted Record - CoT
Total renovation of 17 story Tucson House Building including replacement of mechanical and electrical systems and elevators. Complete update of parking and site areas.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 11/07/2025 | ADMINISTRATIVE v.1 | 11/07/2025 | REQUIRES RESUBMIT |
| 01/28/2025 | COMMERCIAL REVIEW - FULL v.2 | 03/10/2025 | REQUIRES RESUBMIT |
| 10/15/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 10/16/2026 | APPROVED |
| 05/06/2026 | SPECIAL INSPECTION REVIEW v.1 | 05/08/2026 | REQUIRES RESUBMIT |
| 06/06/2025 | COMMERCIAL REVIEW - FULL v.4 | 06/09/2025 | APPROVED |
| 06/09/2025 | RESTAMP - COMMERCIAL v.1 | 06/18/2025 | REQUIRES RESUBMIT |
| 06/18/2025 | RESTAMP - COMMERCIAL v.2 | 06/18/2025 | APPROVED |
| 10/16/2025 | HAST - COMMERCIAL NEW ADD/ALT FAST TRACK v.1 | 11/07/2025 | APPROVED |
| 04/30/2025 | COMMERCIAL REVIEW - FULL v.3 | 05/30/2025 | REQUIRES RESUBMIT |
| 11/18/2025 | ADMINISTRATIVE v.2 | 11/18/2025 | APPROVED |
| 02/05/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 02/12/2026 | REQUIRES RESUBMIT |
| 06/17/2024 | COMMERCIAL REVIEW - FULL v.1 | 07/26/2024 | REQUIRES RESUBMIT |
| 02/23/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.2 | 02/27/2026 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-COM-0624-01123
Permit Status: In review
Permit Description: Restricted Record - CoT
Total renovation of 17 story Tucson House Building including replacement of mechanical and electrical systems and elevators. Complete update of parking and site areas.
Total Outstanding Activity Conditions - 19
| Date | Name |
|---|---|
| 05/07/2026 | Level __: (FRP) FIBER REINFORCE POLIMER PULL TEST THAT ARE ADHERED TO CONCRETE SURFACE. |
| 05/07/2026 | Level __: SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED. |
| 05/07/2026 | Level __: Post-Installed Anchor Inspection Report is required. |
| 05/07/2026 | Level __: SPECIAL INSPECTION FOR REINFORCING STEEL IS REQUIRED. |
| 05/08/2025 | AIR BALANCING REPORT IS REQUIRED. |
| 05/08/2025 | ELEVATOR INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION THAT THE INSPECTION HAS BEEN COMPLETED AND PASSED. |
| 05/08/2025 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. |
| 05/08/2025 | SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED. |
| 05/08/2025 | SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED. |
| 05/08/2025 | SPECIAL INSPECTION FOR HIGH STRENGTH BOLTING IS REQUIRED. |
| 05/08/2025 | SPECIAL INSPECTION FOR OUTDOOR LIGHTING IS REQUIRED. |
| 05/08/2025 | SPECIAL INSPECTION FOR Fire-Resistant Penetrations and Joints IS REQUIRED |
| 05/08/2025 | SPECIAL INSPECTION FOR SPRAY-APPLIED FIRE PROOFING IS REQUIRED. |
| 10/31/2025 | Masonry Inspection Report submittal review is required. |
| 10/31/2025 | Concrete floor repair and strengthening at roof (Level 17) lounge with calculations must be submitted and approved prior to installation of work. |
| 10/31/2025 | Concrete shear head strengthening with calculations must be submitted and approved prior to installation of work. |
| 10/31/2025 | Fiber Reinforced Polymer (FRP) Slab and Wall Strengthening with calculations must be submitted and approved prior to installation of work. |
| 10/31/2025 | SPECIAL INSPECTION FOR Column Shear Strengthening IS REQUIRED |
| 10/31/2025 | SPECIAL INSPECTION FOR STRUCTURAL MASONRY IS REQUIRED. |
Conditions
Permit Number - TC-COM-0624-01123
Permit Status: In review
Permit Description: Restricted Record - CoT
Total renovation of 17 story Tucson House Building including replacement of mechanical and electrical systems and elevators. Complete update of parking and site areas.
| Date | Description | Comments |
|---|---|---|
| 05/07/2026 | Level 16: (FRP) FIBER REINFORCE POLIMER PULL TEST THAT ARE ADHERED TO CONCRETE SURFACE. | |
| 06/17/2024 | Please contact Pima County Addressing to verify the official address. Addressing@pima.gov or 520-724-9512 | |
| 05/08/2025 | Level 16: SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED. | |
| 06/18/2025 | The Contractor you have added to your permit cannot be verified. Please contact staff to have the ROC number added to the account. | |
| 06/18/2025 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 05/08/2025 | Level 16: Post-Installed Anchor Inspection Report is required. | |
| 05/07/2026 | Level 16/17: SPECIAL INSPECTION FOR REINFORCING STEEL IS REQUIRED. | |
| 01/28/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. | |
| 10/16/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. | |
| 10/31/2025 | A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Special inspection certificate(s) need to be provided for masonry and column shear strengthening. | |
| 05/08/2025 | WATER STERILIZATION REPORT IS REQUIRED. |
Outstanding Inspections
Permit Status: In Review
Permit Number: TC-COM-0624-01123
Permite Description: Restricted Record - CoT
Total renovation of 17 story Tucson House Building including replacement of mechanical and electrical systems and elevators. Complete update of parking and site areas.
Total Outstanding Inspections - 24
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2026 | COT - HCME - Venting | N/A | Not Ready | |
| 08/27/2026 | COT - HCBU - Interior Shear Bracing | N/A | Partial Pass | |
| 05/18/2026 | COT - HCPL - Rough Soil | N/A | Partial Pass | |
| 10/06/2026 | COT - HCEL - Electrical Underground | N/A | Partial Pass | |
| 10/21/2026 | COT - HCBU - Excavation/Rebar/Zoning | N/A | Partial Pass | Partial pass. Two slabs for generator pads. Approved. Okay for concrete placement. 10/21/2026 |
| 10/21/2026 | COT - HCEL - Grounding/Bonding | N/A | Partial Pass | 10/21/2026 Partial pass. 13th floor east corridors approved along with units 1320,1321,1322,1319,1323,1318,1324,1316,1325,1315,1326. Pending all wet walls. |
| 08/13/2026 | COT - HCBU - Framing | N/A | Partial Pass | |
| 10/28/2026 | COT - HCME - Mechanical Above Ceiling | N/A | Partial Pass | |
| 09/28/2026 | COT - HCEL - Electrical Above Ceiling | N/A | Partial Pass | |
| 11/04/2026 | COT - HCBU - Building Above Ceiling | N/A | Partial Pass | 11/4/26: Consultation inspection for Laundry room 1st floor. |
| 11/06/2026 | COT - BULD - SWG Clearance | N/A | Partial Pass | Partial pass. Clearance for Southwest gas generator location only. 11/6/2026 |
| 11/06/2026 | COT - HCPL - Gas Pressure Test | N/A | Partial Pass | 11/6/2026 Partial pass. From generator location ran underground and stubbed into wall for future boiler room. |
| 09/10/2026 | COT - HCEL - Electrical Intermediate | N/A | Partial Pass | 9/10/26 13th floor west and 1414 only |
| 11/04/2026 | COT - HCEL - Electrical Final | N/A | Re-inspection required | 11/4/26: 14th floor corridor + electrical/storage rooms final walk: Existing Electrical room - 1. Identify Romex line in existing panel 2. Mark existing electrical panel schedule West mechanical room - 1. Clamps on unistrut above fan coil 2. HVAC refrigerant line supports 3. Conduit supports 4. Verify and label breaker for disconnect 5. Tie in overflow switch on fan coil IDF room - 1. Supports on conduits within 3' 2. Remove low voltage from fire sprinkler pipe Elevator lobby Electrical - 1. Mc clamps 2. Mark electrical panel 3. Clamps off of light Janitors closet - 1. Clamp temporary water lines East Main Electrical room - 1. MC clamps 2. Verify disconnect 3. Remove unused conduit East Existing Electrical room - 1. Replace knockouts on box 2. Relabel panel schedule |
| 11/04/2026 | COT - HCME - Mechanical Final | N/A | Re-inspection required | 11/4/26: 14th floor corridor + electrical/storage rooms final walk: Existing Electrical room - 1. Identify Romex line in existing panel 2. Mark existing electrical panel schedule West mechanical room - 1. Clamps on unistrut above fan coil 2. HVAC refrigerant line supports 3. Conduit supports 4. Verify and label breaker for disconnect 5. Tie in overflow switch on fan coil IDF room - 1. Supports on conduits within 3' 2. Remove low voltage from fire sprinkler pipe Elevator lobby Electrical - 1. Mc clamps 2. Mark electrical panel 3. Clamps off of light Janitors closet - 1. Clamp temporary water lines East Main Electrical room - 1. MC clamps 2. Verify disconnect 3. Remove unused conduit East Existing Electrical room - 1. Replace knockouts on box 2. Relabel panel schedule |
| 11/04/2026 | COT - HCPL - Plumbing Final | N/A | Re-inspection required | 11/4/26: 14th floor corridor + electrical/storage rooms final walk: Existing Electrical room - 1. Identify Romex line in existing panel 2. Mark existing electrical panel schedule West mechanical room - 1. Clamps on unistrut above fan coil 2. HVAC refrigerant line supports 3. Conduit supports 4. Verify and label breaker for disconnect 5. Tie in overflow switch on fan coil IDF room - 1. Supports on conduits within 3' 2. Remove low voltage from fire sprinkler pipe Elevator lobby Electrical - 1. Mc clamps 2. Mark electrical panel 3. Clamps off of light Janitors closet - 1. Clamp temporary water lines East Main Electrical room - 1. MC clamps 2. Verify disconnect 3. Remove unused conduit East Existing Electrical room - 1. Replace knockouts on box 2. Relabel panel schedule |
| 11/23/2026 | COT - HCBU - Building Final | N/A | Partial Pass | 11/23/26 ok to apply for TCO LEVEL 4 LEVEL 16 |
| COT - FCON - Sprinkler - Final | N/A | Not Ready | ||
| 10/05/2026 | ENGR Engineering Final | N/A | Not Ready | Reschedule for 10/12/2026 |
| COT - FCON - Alarm - Final | N/A | Not Ready | ||
| 11/23/2026 | COT - FCON - Fire - Final | N/A | Partial Pass | 16th floor approved for level 4 TCO |
| 08/13/2026 | COT - HCME - Mechanical Intermediate | N/A | Partial Pass | |
| 09/21/2026 | COT - HCPL - Plumbing Intermediate | N/A | Partial Pass | call for shower, diverted vowels and putty packs on floor 14 and 15 OK to proceed |
| 10/14/2026 | COT - HCBU - Firewall/Fire Barrier/Firestop | N/A | Partial Pass | 10/14/26: Okay to apply for level 4 TCO (Floor 15) - pending Fire and Water Sterilization Report. |
Completed Inspections
Permit Status: In Review
Permit Number: TC-COM-0624-01123
Permit Description: Restricted Record - CoT
Total renovation of 17 story Tucson House Building including replacement of mechanical and electrical systems and elevators. Complete update of parking and site areas.
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2026 | PDSD Building Division Pre-Construction Meeting | Passed | ||
| 07/09/2026 | COT - HCPL - Plumbing Above Ceiling | Passed | ||
| 07/30/2026 | BULD - Electrical Clearance | Passed | 1501 N. Oracle Rd. 2M |