Permit: TC-COM-0624-01123
Permit Details
Apply Date:
06/11/2024
Applicant:
Description:
TCO for 15th Floor LVL 4 Total renovation of 17 story Tucson House Building including replacement of mechanical and electrical systems and elevators. Complete update of parking and site areas.
Permit Reviews
Permit Number - TC-COM-0624-01123
Permit Status: Approved
Permit Description: TCO for 15th Floor LVL 4
Total renovation of 17 story Tucson House Building including replacement of mechanical and electrical systems and elevators. Complete update of parking and site areas.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 11/07/2025 | ADMINISTRATIVE v.1 | 11/07/2025 | REQUIRES RESUBMIT |
| 01/28/2025 | COMMERCIAL REVIEW - FULL v.2 | 03/10/2025 | REQUIRES RESUBMIT |
| 10/15/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 10/16/2026 | APPROVED |
| 05/06/2026 | SPECIAL INSPECTION REVIEW v.1 | 05/08/2026 | REQUIRES RESUBMIT |
| 06/06/2025 | COMMERCIAL REVIEW - FULL v.4 | 06/09/2025 | APPROVED |
| 06/09/2025 | RESTAMP - COMMERCIAL v.1 | 06/18/2025 | REQUIRES RESUBMIT |
| 06/18/2025 | RESTAMP - COMMERCIAL v.2 | 06/18/2025 | APPROVED |
| 10/16/2025 | HAST - COMMERCIAL NEW ADD/ALT FAST TRACK v.1 | 11/07/2025 | APPROVED |
| 04/30/2025 | COMMERCIAL REVIEW - FULL v.3 | 05/30/2025 | REQUIRES RESUBMIT |
| 11/18/2025 | ADMINISTRATIVE v.2 | 11/18/2025 | APPROVED |
| 02/05/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 02/12/2026 | REQUIRES RESUBMIT |
| 06/17/2024 | COMMERCIAL REVIEW - FULL v.1 | 07/26/2024 | REQUIRES RESUBMIT |
| 02/23/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.2 | 02/27/2026 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-COM-0624-01123
Permit Status: Approved
Permit Description: TCO for 15th Floor LVL 4
Total renovation of 17 story Tucson House Building including replacement of mechanical and electrical systems and elevators. Complete update of parking and site areas.
Total Outstanding Activity Conditions - 19
| Date | Name |
|---|---|
| 05/07/2026 | Level __: (FRP) FIBER REINFORCE POLIMER PULL TEST THAT ARE ADHERED TO CONCRETE SURFACE. |
| 05/07/2026 | Level __: SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED. |
| 05/07/2026 | Level __: Post-Installed Anchor Inspection Report is required. |
| 05/07/2026 | Level __: SPECIAL INSPECTION FOR REINFORCING STEEL IS REQUIRED. |
| 05/08/2025 | AIR BALANCING REPORT IS REQUIRED. |
| 05/08/2025 | ELEVATOR INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION THAT THE INSPECTION HAS BEEN COMPLETED AND PASSED. |
| 05/08/2025 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. |
| 05/08/2025 | SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED. |
| 05/08/2025 | SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED. |
| 05/08/2025 | SPECIAL INSPECTION FOR HIGH STRENGTH BOLTING IS REQUIRED. |
| 05/08/2025 | SPECIAL INSPECTION FOR OUTDOOR LIGHTING IS REQUIRED. |
| 05/08/2025 | SPECIAL INSPECTION FOR Fire-Resistant Penetrations and Joints IS REQUIRED |
| 05/08/2025 | SPECIAL INSPECTION FOR SPRAY-APPLIED FIRE PROOFING IS REQUIRED. |
| 10/31/2025 | Masonry Inspection Report submittal review is required. |
| 10/31/2025 | Concrete floor repair and strengthening at roof (Level 17) lounge with calculations must be submitted and approved prior to installation of work. |
| 10/31/2025 | Concrete shear head strengthening with calculations must be submitted and approved prior to installation of work. |
| 10/31/2025 | Fiber Reinforced Polymer (FRP) Slab and Wall Strengthening with calculations must be submitted and approved prior to installation of work. |
| 10/31/2025 | SPECIAL INSPECTION FOR Column Shear Strengthening IS REQUIRED |
| 10/31/2025 | SPECIAL INSPECTION FOR STRUCTURAL MASONRY IS REQUIRED. |
Conditions
Permit Number - TC-COM-0624-01123
Permit Status: Approved
Permit Description: TCO for 15th Floor LVL 4
Total renovation of 17 story Tucson House Building including replacement of mechanical and electrical systems and elevators. Complete update of parking and site areas.
| Date | Description | Comments |
|---|---|---|
| 05/07/2026 | Level 16: (FRP) FIBER REINFORCE POLIMER PULL TEST THAT ARE ADHERED TO CONCRETE SURFACE. | |
| 06/17/2024 | Please contact Pima County Addressing to verify the official address. Addressing@pima.gov or 520-724-9512 | |
| 05/08/2025 | Level 16: SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED. | |
| 06/18/2025 | The Contractor you have added to your permit cannot be verified. Please contact staff to have the ROC number added to the account. | |
| 06/18/2025 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 05/08/2025 | Level 16: Post-Installed Anchor Inspection Report is required. | |
| 05/07/2026 | Level 16/17: SPECIAL INSPECTION FOR REINFORCING STEEL IS REQUIRED. | |
| 01/28/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. | |
| 10/16/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. | |
| 10/31/2025 | A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Special inspection certificate(s) need to be provided for masonry and column shear strengthening. | |
| 05/08/2025 | WATER STERILIZATION REPORT IS REQUIRED. |
Outstanding Inspections
Permit Status: Approved
Permit Number: TC-COM-0624-01123
Permite Description: TCO for 15th Floor LVL 4
Total renovation of 17 story Tucson House Building including replacement of mechanical and electrical systems and elevators. Complete update of parking and site areas.
Total Outstanding Inspections - 23
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2026 | COT - HCME - Venting | N/A | Not Ready | |
| 07/15/2026 | COT - HCPL - Gas Pressure Test | N/A | Not Applicable | |
| 07/27/2026 | COT - BULD - SWG Clearance | N/A | Not Ready | |
| 08/27/2026 | COT - HCBU - Interior Shear Bracing | N/A | Partial Pass | |
| 05/18/2026 | COT - HCPL - Rough Soil | N/A | Partial Pass | |
| 10/06/2026 | COT - HCEL - Electrical Underground | N/A | Partial Pass | |
| 10/12/2026 | COT - HCBU - Building Final | N/A | Not Ready | 15th floor Corridors and lobby’s General Notes Demo old telecom equipment in closets 1510 Storage Label mechanical unit Seal around fire hose cabinet Clamp on MC to mechanical shut off within 12”, label circuit Fire caulking around mechanical unit duct Storage 15-06 check w/ electricians on light IDF Add covers to fire alarm Foam packs in conduits Elevator Lobby General Expansion Joints Small Electrical room Plug in knockout Janitors closet Missing mop sink Missing access panel Check penetrations Trash chute room Cap junction boxes 1517 electrical room Fill old electrical box on ceiling Fire penetrations Feeders Straps on MC 12” of box East abandoned electrical room Seal penetrations stairwells fire caulk penetrations Check knockouts Corridors Labels on outlets for circuit |
| 10/05/2026 | ENGR Engineering Final | N/A | Not Ready | Reschedule for 10/12/2026 |
| 10/14/2026 | COT - HCBU - Firewall/Fire Barrier/Firestop | N/A | Partial Pass | 10/14/26: Okay to apply for level 4 TCO (Floor 15) - pending Fire and Water Sterilization Report. |
| 10/15/2026 | COT - FCON - Fire - Final | N/A | Partial Pass | approved for level 4 TCO 15th floor only |
| 10/21/2026 | COT - HCBU - Excavation/Rebar/Zoning | N/A | Partial Pass | Partial pass. Two slabs for generator pads. Approved. Okay for concrete placement. 10/21/2026 |
| 10/21/2026 | COT - HCEL - Grounding/Bonding | N/A | Partial Pass | 10/21/2026 Partial pass. 13th floor east corridors approved along with units 1320,1321,1322,1319,1323,1318,1324,1316,1325,1315,1326. Pending all wet walls. |
| 09/10/2026 | COT - HCEL - Electrical Intermediate | N/A | Partial Pass | 9/10/26 13th floor west and 1414 only |
| 09/21/2026 | COT - HCPL - Plumbing Intermediate | N/A | Partial Pass | call for shower, diverted vowels and putty packs on floor 14 and 15 OK to proceed |
| 08/13/2026 | COT - HCBU - Framing | N/A | Partial Pass | |
| 08/13/2026 | COT - HCME - Mechanical Intermediate | N/A | Partial Pass | |
| 10/28/2026 | COT - HCME - Mechanical Above Ceiling | N/A | Partial Pass | |
| 09/28/2026 | COT - HCEL - Electrical Above Ceiling | N/A | Partial Pass | |
| COT - HCEL - Electrical Final | N/A | Scheduled | ||
| COT - HCME - Mechanical Final | N/A | Scheduled | ||
| COT - HCPL - Plumbing Final | N/A | Scheduled | ||
| COT - HCBU - Building Above Ceiling | N/A | Scheduled | ||
| COT - FCON - Sprinkler - Final | N/A | Not Ready |
Completed Inspections
Permit Status: Approved
Permit Number: TC-COM-0624-01123
Permit Description: TCO for 15th Floor LVL 4
Total renovation of 17 story Tucson House Building including replacement of mechanical and electrical systems and elevators. Complete update of parking and site areas.
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2026 | PDSD Building Division Pre-Construction Meeting | Passed | ||
| 07/09/2026 | COT - HCPL - Plumbing Above Ceiling | Passed | ||
| 07/30/2026 | BULD - Electrical Clearance | Passed | 1501 N. Oracle Rd. 2M |
Scheduled Inspections
Scheduled Inspections - TC-COM-0624-01123
Status: Approved
Description: TCO for 15th Floor LVL 4
Total renovation of 17 story Tucson House Building including replacement of mechanical and electrical systems and elevators. Complete update of parking and site areas.
| Scheduled Date | Description | Entered By | Entered Date |
|---|---|---|---|
| 11/04/2026 | COT - HCBU - Building Above Ceiling | Scheduled | |
| 11/04/2026 | COT - HCME - Mechanical Final | Scheduled | |
| 11/04/2026 | COT - HCEL - Electrical Final | Scheduled | |
| 11/04/2026 | COT - HCPL - Plumbing Final | Scheduled |