| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2026 | COT - HCBU - Building Final | Not Ready | ||
| 10/12/2026 | COT - HCBU - Building Final | Not Ready | 15th floor Corridors and lobby’s General Notes Demo old telecom equipment in closets 1510 Storage Label mechanical unit Seal around fire hose cabinet Clamp on MC to mechanical shut off within 12”, label circuit Fire caulking around mechanical unit duct Storage 15-06 check w/ electricians on light IDF Add covers to fire alarm Foam packs in conduits Elevator Lobby General Expansion Joints Small Electrical room Plug in knockout Janitors closet Missing mop sink Missing access panel Check penetrations Trash chute room Cap junction boxes 1517 electrical room Fill old electrical box on ceiling Fire penetrations Feeders Straps on MC 12” of box East abandoned electrical room Seal penetrations stairwells fire caulk penetrations Check knockouts Corridors Labels on outlets for circuit |