Permit Details

Status:
Issued
Type:
Commercial Building
Address NEW:
6024 S KIRTLEY DR
Apply Date:
04/17/2025
Applicant:
George Zazueta
Description:
FIRE RESTORATION TO SFR - FIRE IN UPSTAIRS MASTER BEDROOM CLOSET- NEED TO DO ROOF REPAIR, 7 TRUSSES, ELECTRICAL, PLUMBING, HVAC, INSULATION AND DRYWALL

Permit Reviews

Permit Number - TC-COM-0425-00783
Permit Status: Issued
Permit Description: FIRE RESTORATION TO SFR - FIRE IN UPSTAIRS MASTER BEDROOM CLOSET- NEED TO DO ROOF REPAIR, 7 TRUSSES, ELECTRICAL, PLUMBING, HVAC, INSULATION AND DRYWALL
Start Date Submittal Complete Date Status  
10/03/2025 ADMINISTRATIVE v.2 10/06/2025 APPROVED Review Details
10/03/2025 RESTAMP - COMMERCIAL v.1 10/06/2025 APPROVED Review Details
04/23/2025 COMMERCIAL REVIEW - FULL v.2 05/22/2025 REQUIRES RESUBMIT Review Details
06/17/2025 COMMERCIAL REVIEW - FULL v.5 07/02/2025 APPROVED Review Details
08/14/2025 COMMERCIAL REVIEW - FULL REVISION v.3 09/08/2025 APPROVED Review Details
05/30/2025 COMMERCIAL REVIEW - FULL v.3 05/30/2025 REQUIRES RESUBMIT Review Details
04/22/2025 COMMERCIAL REVIEW - FULL v.1 04/22/2025 REQUIRES RESUBMIT Review Details
08/11/2025 COMMERCIAL REVIEW - FULL REVISION v.2 08/11/2025 REQUIRES RESUBMIT Review Details
06/16/2025 COMMERCIAL REVIEW - FULL v.4 06/16/2025 REQUIRES RESUBMIT Review Details
10/03/2025 ADMINISTRATIVE v.1 10/03/2025 REQUIRES RESUBMIT Review Details
12/17/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 12/22/2025 APPROVED Review Details
08/08/2025 COMMERCIAL REVIEW - FULL REVISION v.1 08/08/2025 REQUIRES RESUBMIT Review Details
07/02/2025 RESTAMP - COMMERCIAL v.1 07/07/2025 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0425-00783
Permit Status: Issued
Permit Description: FIRE RESTORATION TO SFR - FIRE IN UPSTAIRS MASTER BEDROOM CLOSET- NEED TO DO ROOF REPAIR, 7 TRUSSES, ELECTRICAL, PLUMBING, HVAC, INSULATION AND DRYWALL
Total Outstanding Activity Conditions - 1
Date Name
10/06/2025 WATER STERILIZATION REPORT IS REQUIRED.

Conditions

Permit Number - TC-COM-0425-00783
Permit Status: Issued
Permit Description: FIRE RESTORATION TO SFR - FIRE IN UPSTAIRS MASTER BEDROOM CLOSET- NEED TO DO ROOF REPAIR, 7 TRUSSES, ELECTRICAL, PLUMBING, HVAC, INSULATION AND DRYWALL
Date Description Comments
05/14/2025 AIR BALANCING REPORT IS REQUIRED.
07/02/2025 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
07/03/2025 THIS PERMIT IS A FIRE RESTORATION TO SINGLE FAMILY RESIDENCE-ANY OTHER USE WILL REQUIRE A TENANT IMPROVEMENT PERMIT
05/12/2025 Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-0425-00783
Permite Description: FIRE RESTORATION TO SFR - FIRE IN UPSTAIRS MASTER BEDROOM CLOSET- NEED TO DO ROOF REPAIR, 7 TRUSSES, ELECTRICAL, PLUMBING, HVAC, INSULATION AND DRYWALL
Total Outstanding Inspections - 7
Last Inspection Date Description Inspector Results Comments
07/23/2025 COT - FCON - Fire - Final N/A Not Applicable
12/24/2025 COT - HCPL - Plumbing Intermediate N/A Re-inspection required (with fee) 12-24-25: fire foam penetrations upstairs & from garage to living spaces-see previous notes, hot pex lines not secured, missing blocking at ends of shower-see detail 808/AD2 and flange detail for more, missing greywater-see previous notes. Stopped inspection-not ready.
Note: framing inspection has been scheduled.
02/18/2026 COT - LCPL - Rough Soil N/A Not Applicable
02/18/2026 COT - LCME - Mechanical Intermediate N/A Re-inspection required 2/18/26: per previous inspection noted on 2-5-26 and 1/6/26 (flex duct shall be properly secured throughout), per inspection on 1/6/26 (B-vent shall maintain 1" clearance from combustibles at 2nd story), drain lines running horizontal between floors shall be properly secured every 4', properly secure walls at first floor closet bedroom and 2nd floor master bedroom, all penetrations at vapor barrier shall be sealed (2nd floor, marked with red marker).
09/03/2026 COT - LCPL - Plumbing Final N/A Re-inspection required 9-3-26: missing anti-tip device and stove, missing dishwasher and hammer arrestor, missing hammer arrestor at refrigerator, missing receptacle cover/replace receptacle to weather resistant gfci at exterior wall adjacent to back sliding glass door, missing vacuum breaker at hose bib, a fire rated door from garage to home is required, threshold at garage does not meet ADA standards, missing receptacle covers at garage, pressure relief valve at water heater not connected, remove all debris from back yard. STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE NOTED. 2ND FLOOR NOT WALKED.
09/03/2026 COT - LCBU - Building Final N/A Re-inspection required 9-3-26: missing anti-tip device and stove, missing dishwasher and hammer arrestor, missing hammer arrestor at refrigerator, missing receptacle cover/replace receptacle to weather resistant gfci at exterior wall adjacent to back sliding glass door, missing vacuum breaker at hose bib, a fire rated door from garage to home is required, threshold at garage does not meet ADA standards, missing receptacle covers at garage, pressure relief valve at water heater not connected, remove all debris from back yard. STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE NOTED. 2ND FLOOR NOT WALKED.
07/21/2025 COT - HCBU - TCO N/A Not Ready 7-21-25: not ready for TCO.

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-0425-00783
Permit Description: FIRE RESTORATION TO SFR - FIRE IN UPSTAIRS MASTER BEDROOM CLOSET- NEED TO DO ROOF REPAIR, 7 TRUSSES, ELECTRICAL, PLUMBING, HVAC, INSULATION AND DRYWALL
Total Completed Inspections - 14
Date Description Inspector Results Comments
07/23/2025 ENGR Engineering Final Passed Site is clear from any repair work.
11/14/2025 BULD - Electrical Clearance Passed 11-14-25: okay to energize meter 157584487. RECN issued to TEP.
12/05/2025 COT - HCPL - Gas Pressure Test Passed 12.4.25
Approved
12/11/2025 COT - LCEL - Electrical Intermediate Passed 12-11-25: electrical intermediates approved.
Schedule plumbing & mechanical intermediates when ready.
02/18/2026 COT - HCPL - Plumbing Intermediate Passed
02/18/2026 COT - LCEL - Electrical Above Ceiling Passed
02/18/2026 COT - LCBU - Roof Nailing Passed
02/19/2026 COT - LCME - Mechanical Intermediate Passed
02/19/2026 COT - LCBU - Framing Passed
03/27/2026 COT - HCBU - Interior Shear Bracing Passed 3-27-26: interior shear bracing approved. Okay to tape & texture.
05/18/2026 COT - LCEL - Electrical Final Passed 5/18/2026 approved. All corrections were made.
09/02/2026 COT - LCME - Mechanical Final Passed
09/03/2026 TRSP - ROW - Notice of Completion Passed no impact to right of way, restoration strictly limited to the structure on private property
10/22/2026 COT - BULD - SWG Clearance Passed 10/22/26: okay to install gas meter-SWG clearance issued.

Documents

File Name Document Type  
AZ DUCT TESTING_V1.PDF DOCUMENTS VIEW
3_PLAN_SET V2_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
TC-COM-0425-00783_COMMENT_RESPONSE_LETTER 10-03-25_V1.PDF DOCUMENTS VIEW
TC-COM-0425-00783_ELECTRICAL_REVISION_NARRATIVE V2_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-COMMENT RESPONSE LETTER AND CONSTRUCTION PLANS_V2.PDF DOCUMENTS VIEW