Permit: TC-COM-0425-00783

Parcel: 140327000


Addresses:

6024 S KIRTLEY DR

Inspection Status: Re-inspection required

Inspection History: COT - HCBU - Interior Shear Bracing 

Date Description Inspector Results Comments
03/20/2026 COT - HCBU - Interior Shear Bracing  Re-inspection required Shear walls not per schedule. Provide 5/8" type x at garage ceiling. Screws cannot be less than 3/8" from edges. 3/20/2026
03/23/2026 COT - HCBU - Interior Shear Bracing  Re-inspection required (with fee) 3-23-26: 5/8" type x drywall is required at garage ceiling, add screws no closer than 3/8" from edges/joints-noted several areas where screws were installed directly over joints. Reschedule inspection when corrections are made.
03/26/2026 COT - HCBU - Interior Shear Bracing  Re-inspection required (with fee) 3-26-26: add screws to marked locations throughout each level. As previously mentioned, screws are required to be installed no closer than 3/8" from edges/joints & cannot over penetrate drywall more than 1/32". Make corrections-reinspection fee applies and schedule when ready
03/27/2026 COT - HCBU - Interior Shear Bracing  Passed 3-27-26: interior shear bracing approved. Okay to tape & texture.