Inspection Status: Re-inspection required
Inspection History: COT - HCBU - Interior Shear Bracing
| Date |
Description |
Inspector |
Results |
Comments |
| 03/20/2026 |
COT - HCBU - Interior Shear Bracing |
|
Re-inspection required |
Shear walls not per schedule. Provide 5/8" type x at garage ceiling. Screws cannot be less than 3/8" from edges. 3/20/2026 |
| 03/23/2026 |
COT - HCBU - Interior Shear Bracing |
|
Re-inspection required (with fee) |
3-23-26: 5/8" type x drywall is required at garage ceiling, add screws no closer than 3/8" from edges/joints-noted several areas where screws were installed directly over joints. Reschedule inspection when corrections are made. |
| 03/26/2026 |
COT - HCBU - Interior Shear Bracing |
|
Re-inspection required (with fee) |
3-26-26: add screws to marked locations throughout each level. As previously mentioned, screws are required to be installed no closer than 3/8" from edges/joints & cannot over penetrate drywall more than 1/32". Make corrections-reinspection fee applies and schedule when ready |
| 03/27/2026 |
COT - HCBU - Interior Shear Bracing |
|
Passed |
3-27-26: interior shear bracing approved. Okay to tape & texture. |