Status:
Expired
Type:
Residential Building - One or Two Family
Apply Date:
04/04/2022
Applicant:
Juan Cruz
Description:
DUPLEX

Permit Reviews

Permit Number - T22CM02434
Permit Status: Expired
Permit Description: DUPLEX
Start Date Submittal Complete Date Status  
04/04/2022 RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO 04/21/2022 COMPLETED Review Details
04/09/2026 RESIDENTIAL NEW DWELLING REVISION v.2 N/A REQUIRES RESUBMIT Review Details
05/19/2026 RESIDENTIAL NEW DWELLING REVISION v.3 N/A REQUIRES RESUBMIT Review Details
05/14/2025 RESIDENTIAL NEW DWELLING REVISION v.1 05/14/2025 REQUIRES RESUBMIT Review Details
10/10/2024 RESIDENTIAL NEW DWELLING v.2 11/18/2024 APPROVED Review Details
12/20/2022 RESIDENTIAL NEW DWELLING v.1 01/04/2023 REQUIRES RESUBMIT Review Details

Outstanding Activity Conditions

Permit Number - T22CM02434
Permit Status: Expired
Permit Description: DUPLEX
Total Outstanding Activity Conditions - 2
Date Name
05/19/2026 The unit numbers on the plan set do not match the addresses listed on the permit. Please resubmit the plans with the correct unit numbers. Do not make any other changes to the plans. Any revisions beyond correcting the addresses will require a full review and may result in additional fees. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
10/17/2024 Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building.

Outstanding Inspections

Permit Status: Expired
Permit Number: T22CM02434
Permite Description: DUPLEX
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
12/10/2025 COT - RSBU - Firewall/Fire Barrier/Firestop N/A Not Ready
12/09/2025 COT - RSPL - Gas Pressure Test N/A Re-inspection required 12-9-25: not under test-Missing shut off valves.
12/09/2025 COT - BULD - SWG Clearance N/A Re-inspection required 12-9-25: missing shut off valves and system was not under test. A 15 psi gauge is required and must be under test a minimum of 15 minutes at 15 psi.
05/01/2026 RSBU - Building Final N/A Re-inspection required 5-1-26: arch fault breakers are required for each habitable location, install R3 insulation at hose bibs, and vacuum breakers, unit 2-open neutral at kitchen gfci, anti tip device missing at each unit, paint exterior plastic , add plastic bushings to protect wiring at minimum splits, seal mini split whips at exterior walls. Main water line inspection was never inspected- please expose several pockets so that we may verify trench depth and tracer wires. Schedule all pending inspections at same time.

Completed Inspections

Permit Status: Expired
Permit Number: T22CM02434
Permit Description: DUPLEX
Total Completed Inspections - 7
Date Description Inspector Results Comments
09/11/2025 COT - RSPL - Rough Soil Passed 9-11-25: underground plumbing & sewer connection verified per plans-okay to backfill with shading materials.
09/11/2025 COT - RSPL - Sewer Passed 9-11-25: underground plumbing & sewer connection verified per plans-okay to backfill with shading materials.
01/21/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed 01/21/2026
All corrections made to 12/10/25 inspection.
01/21/2026 COT - RSBU - Firewall/Fire Barrier/Firestop Passed 01/21/2026
Approved per plan, common firewall with putty at receptacles and sealed edges and penetrations from top to bottom through 5/8" rated gypsum.
01/21/2026 COT - RSPL - Gas Pressure Test Passed 01/21/2026
Both lines holding under test.
01/21/2026 COT - BULD - SWG Clearance Passed 01/21/2026
Clearance Southwest Gas. Verified all gas fixtures trapped and shutoff valves downstream.
04/22/2026 BULD - Electrical Clearance Passed Eco approve for units 2 and 3