Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Address:
6951 S PARK AV
Apply Date:
07/16/2014
Applicant:
METRO TUCSON EXPEDITING & DEVELOPMENT
Description:
NEW METAL HANGAR
Architects:
  • FRANKS, MICHAEL WILLIAM
Contractors:
  • LANG WYATT CONSTRUCTION ,

Permit Reviews

Permit Number - T14CM04464
Permit Status: C of o
Permit Description: NEW METAL HANGAR
Start Date Submittal Complete Date Status  
07/16/2014 PLANS OK TO SUBMIT - COMM 07/16/2014 COMPLETED Review Details
07/17/2014 COMMERCIAL - NEW 08/06/2014 COMPLETED Review Details
08/06/2014 RESUBMITTAL - TI ALL 09/02/2014 COMPLETED Review Details
09/02/2014 REVISION - - 1ST 09/02/2014 COMPLETED Review Details
09/02/2014 REVISION - - 1ST 09/05/2014 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T14CM04464
Permit Status: C of o
Permit Description: NEW METAL HANGAR
Total Outstanding Activity Conditions - 1
Date Name
07/16/2014 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T14CM04464
Permit Description: NEW METAL HANGAR
Total Completed Inspections - 24
Date Description Inspector Results Comments
07/24/2014 FIRE SPKLR - UG, PIPING, HYDRO CBASALDUA Approved
07/24/2014 FIRE SPKLR - UG PIPING FLUSH CBASALDUA Approved
09/10/2014 ELECTRIC - UNDERGROUND RCAMACHO Approved IVRS - Inspection :*
12/30/2014 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
12/30/2014 PLUMBING - FINAL MRAMBER Approved IVRS - Inspection :*
12/30/2014 PLUMBING - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
12/30/2014 PLUMBING - ROUGH, SOIL MRAMBER Approved IVRS - Inspection :*
12/30/2014 ELECTRIC - FINAL MRAMBER Approved IVRS - Inspection :*
12/30/2014 ELECTRIC - OUTDOOR LIGHTING MRAMBER Approved IVRS - Inspection :*
12/30/2014 ELECTRIC - TEMP POWER FOR TEST MRAMBER Approved IVRS - Inspection :*
12/30/2014 ELECTRIC - ABOVE CEILING MRAMBER Approved IVRS - Inspection :*
12/30/2014 ELECTRIC - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
12/30/2014 BUILDING - FINAL MRAMBER Approved IVRS - Inspection :*
12/30/2014 BUILDING - PROGRESS MRAMBER Approved IVRS - Inspection :*
12/30/2014 FRAMING MRAMBER Approved IVRS - Inspection :*
12/30/2014 EXCAVATION/LAYOUT REBAR & ZON MRAMBER Approved IVRS - Inspection :*
12/31/2014 FIRE - FINAL CSCHULTZ Approved 1. Missing set of emergency lights eastside of building x 4
2. Need address numbers posted on both sides building for TFD and Airport Fire
3. Need extinguishers posted every 50 feet travel distance 2A-20BC size
Did give permission to allow then to pull two planes into the hanger to mark out floors for painting lines BUT NO WORK ALLOWED ON PLANES must move planes out when marking is completed.
12/31/2014 FIRE SPKLR - FINAL CSCHULTZ Approved Pre-action system failed
Need as bults for the sprinkler system changes and need to make changes to sprinkler system per approved new sprinkler plans
12/31/2014 FIRE - ALARM FINAL CSCHULTZ Approved Pre-action system failed
12/31/2014 ENGINEERING - FINAL RLEDONNE Approved
01/07/2015 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved Fire extinguishers mounted on walls every 50 feet 4A-20BC, other fire extinguishers while working on planes shall be within 50 feet of employees.
Pre-action - PASSED
200 psi test for 2 hours for new sprinkler piping - PASSED
Sprinkler piping changes per revised plans - APPROVED
01/07/2015 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved NEED TO DO 200 PSI TEST ON ALL NEW PIPING PER REVISED PLANS
01/07/2015 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved 200 PSI FOR 2 HOURS AND FLUSHED BOTH HOSE LINES
01/08/2015 MECHANICAL - INTERMEDIATE MRAMBER Approved PER FINAL

Documents

File Name Document Type  
C OF O_01-08-2015.TIF CERT OF OCC VIEW
None DOCUMENTS VIEW