Permit: T14CM04464

Parcel: 14043011A


Addresses:

6951 S PARK AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM04464

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/07/2015 FIRE - FINAL Approved Fire extinguishers mounted on walls every 50 feet 4A-20BC, other fire extinguishers while working on planes shall be within 50 feet of employees.
Pre-action - PASSED
200 psi test for 2 hours for new sprinkler piping - PASSED
Sprinkler piping changes per revised plans - APPROVED
12/31/2014 FIRE - FINAL Denied 1. Missing set of emergency lights eastside of building x 4
2. Need address numbers posted on both sides building for TFD and Airport Fire
3. Need extinguishers posted every 50 feet travel distance 2A-20BC size
Did give permission to allow then to pull two planes into the hanger to mark out floors for painting lines BUT NO WORK ALLOWED ON PLANES must move planes out when marking is completed.
12/30/2014 FIRE - FINAL Denied Pre-action system failed
Need to test battery back up lights
Need as bults for the sprinkler system changes