Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM04464
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/07/2015 | FIRE - FINAL | Approved | Fire extinguishers mounted on walls every 50 feet 4A-20BC, other fire extinguishers while working on planes shall be within 50 feet of employees. Pre-action - PASSED 200 psi test for 2 hours for new sprinkler piping - PASSED Sprinkler piping changes per revised plans - APPROVED |
|
12/31/2014 | FIRE - FINAL | Denied | 1. Missing set of emergency lights eastside of building x 4 2. Need address numbers posted on both sides building for TFD and Airport Fire 3. Need extinguishers posted every 50 feet travel distance 2A-20BC size Did give permission to allow then to pull two planes into the hanger to mark out floors for painting lines BUT NO WORK ALLOWED ON PLANES must move planes out when marking is completed. |
|
12/30/2014 | FIRE - FINAL | Denied | Pre-action system failed Need to test battery back up lights Need as bults for the sprinkler system changes |