Permit Number: T14CM04464
Parcel: 14043011A

Address:
6951 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T14CM04464
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2014 KEN BROUILLETTE FIRE REVIEW Approved
07/25/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.1; DETAIL 4: PROVIDE THE STEEL PIPE SIZE AND THE CONCRETE PIER SIZE.
2. SHEET A4.0; KEYNOTES: NOTE 1 WAS NOT LOCATED ON THE ELEVATIONS. VERIFY.
3. SHEET A4.1; SOUTH ELEVATION: THE KEYNOTE INDICATOR AT THE BOLLARD SHOULD BE COMPLETED.
4. SHEET A4.1; SOUTH AND WEST ELEVATIONS: NOTE 4 IS INDICATED AT THE RIDGE VENT ON BOTH ELEVATIONS. REVISE.
5. SHEET A5.0; KEYNOTES: NOTES 3 AND 4 WERE NOT LOCATED ON THE ELEVATIONS. VERIFY.
6. SHEET A5.0; KEYNOTES: NOTE 12 IS INDICATED ON THE HANGAR SECTION 1 ABOVE THE TAIL OVERHEAD DOOR. VERIFY.
7. SHEET S0.1; GENERAL STRUCTURAL NOTES (FOUNDATIONS): NOTE 1 INDICATES A SHALLOW SPREAD FOOTING DESIGN WAS RECOMMENDED IN THE SOILS REPORT. THE SOILS REPORT INVESTIGATED ONLY DRILLED SHAFT FOUNDATIONS. REVISE SHEET S0.1.
8. SHEET S1.0 (FOUNDATION PLAN); GEOTECHNICAL REPORT (LAST PAGE): THE TABLE IN THE GEOTECHNICAL REPORT INDICATES 18' MINIMUM EMBEDMENT LENGTH OF DRILLED PIERS ALONG GRIDS A AND A.3, AND 16' MINIMUM EMBEDMENT LENGTH ALONG GRIDS B THROUGH G. SHOULD THE CAISSON FOOTING CF1 IN THE FOOTING SCHEDULE ON SHEET S1.0 BE CHANGED TO 16'? VERIFY.
9. SHEET S1.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE "TYP" AND "SIM" NOTES AT THE DETAIL REFERENCES ON THE PLAN.
10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/28/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The existing 10" public sewer that is located within the boundaries of the proposed hangar is constructed of vitreous clay pipe. This is not approved for use under a building. Reference: Section 702.2, IPC 2012.
2. Provide the slope of the rain gutters. Reference: Section 1106.6, IPC 2012.
07/28/2014 ROBERT SHERRY WATER REVIEW Reqs Change Show the location of the new reduced pressure backflow preventer for the water service to the new hangar on the site plan.
07/29/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.
07/29/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
07/31/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/06/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed