Inspection Status: Denied
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T14CM04464
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/07/2015 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 200 PSI FOR 2 HOURS AND FLUSHED BOTH HOSE LINES | |
01/07/2015 | FIRE SPKLR - OH PIPING & HYDRO | Denied | NEED TO DO 200 PSI TEST ON ALL NEW PIPING PER REVISED PLANS | |
01/07/2015 | FIRE SPKLR - OH PIPING & HYDRO | Approved | Fire extinguishers mounted on walls every 50 feet 4A-20BC, other fire extinguishers while working on planes shall be within 50 feet of employees. Pre-action - PASSED 200 psi test for 2 hours for new sprinkler piping - PASSED Sprinkler piping changes per revised plans - APPROVED |