Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2015 | FIRE SPKLR - FINAL | Approved | Fire extinguishers mounted on walls every 50 feet 4A-20BC, other fire extinguishers while working on planes shall be within 50 feet of employees. Pre-action - PASSED 200 psi test for 2 hours for new sprinkler piping - PASSED Sprinkler piping changes per revised plans - APPROVED |
|
| 12/31/2014 | FIRE SPKLR - FINAL | Denied | Pre-action system failed Need as bults for the sprinkler system changes and need to make changes to sprinkler system per approved new sprinkler plans |
|
| 12/30/2014 | FIRE SPKLR - FINAL | Denied | Pre-action system failed Need as bults for the sprinkler system changes |