Description:
TI; RESTAURANT
Contractors:
  • AIR VELOCITY INCORPORATED

Permit Reviews

Permit Number - T11CM02865
Permit Status: Expired
Permit Description: TI; RESTAURANT
Start Date Submittal Complete Date Status  
01/13/2012 REVISION - - 2ND 01/13/2012 COMPLETED Review Details
04/23/2012 REVISION - - 3RD 05/07/2012 COMPLETED Review Details
06/04/2012 REVISION - - 4TH 06/29/2012 COMPLETED Review Details
09/06/2011 PLANS OK TO SUBMIT - COMM 09/06/2011 COMPLETED Review Details
09/06/2011 COMMERCIAL - TI 10/13/2011 COMPLETED Review Details
10/13/2011 RESUBMITTAL 10/17/2011 COMPLETED Review Details
10/17/2011 RESUBMITTAL 11/22/2011 COMPLETED Review Details
11/23/2011 RESUBMITTAL 12/13/2011 COMPLETED Review Details
12/13/2011 RESUBMITTAL 12/21/2011 COMPLETED Review Details
12/29/2011 REVISION - - 1ST 01/13/2012 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T11CM02865
Permit Status: Expired
Permit Description: TI; RESTAURANT
Total Outstanding Activity Conditions - 1
Date Name
09/06/2011 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T11CM02865
Permite Description: TI; RESTAURANT
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
PLUMBING - GAS PRESS TEST FNL N/A Not Inspected

Completed Inspections

Permit Status: Expired
Permit Number: T11CM02865
Permit Description: TI; RESTAURANT
Total Completed Inspections - 33
Date Description Inspector Results Comments
12/22/2011 PLUMBING - PRE SLAB BBENEDON Approved IVRS - Inspection :*
NOT UNDER TEST
"NEED LIGHTS TO SEE"
12/22/2011 FRAMING DWALKER Approved IVRS - Inspection :
See detailed listing on site.| 999*
12/27/2011 ELECTRIC - UNDERGROUND RHOLLAND Approved IVRS - Inspection :*
1) INSTALL VDV CABLEING 725.8, 800.24
2) WIRING AT SPRINKLER VALVE IN WALL
OK UNDERGROUND NOTE SOME RUNS HAVE 360 DEGREE (GROUND)-WILL NEED JUNCTION BOXES COMMING OUT OF WALLS
OK WALL EXCEPT AS NOTED
3) 1200 AMP SES TO HAVE CLEARANCES PER 110.26(c)
12/27/2011 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*
12/28/2011 MECHANICAL - HOODS MRAMBER Approved IVRS - Inspection :*
1) CONTRACTOR NEEDS TO BE ON SITE FOR INSPECTION
12/28/2011 PLUMBING - ROUGH, SOIL BBENEDON Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE SAFE LIGHTING FOR INSPECTION
2) REMOVE ROCKS AND MUD
3) ALL PIPING REQUIRES CONTINOUS SUPPORT
4) SHADE PIPEING WITH CLEAN FILL
5) INSTALL PIPING PER PLAN AND PROVIDE DOCUMENTATION FOR ANY CHANGES-MANY SIZE DISCREPENCIES
6) COMBINATION WASTE AND VENT REQUIRES 2" FLOOR SINKS WITH A 2 X 3 INCREASER ON TAIL PIECE AS SHOWN ON YOUR PLAN
7) THE POINT OF VENT FOR ALL VENTS SHALL BE TAKEN OFF ABOVE THE CENTER LINE OF THE DRAIN SERVED (ROLL UP AT 45 DEGREE MINIMUM)
8) RE-VENTS SHALL BE 6" ABOVE THE FLOOD LEVEL OF THE HIGHEST FLANGE
9) CORRECT SLOPE
10) GW HAS BACK PITCH
11) ALL DRAIN LINES REQUIRE FULL SIZED CLEANOUTS
12) A DIRECT CONNECTION IS REQUIRED PER UPC 704.3 FOR ALL FIXTURES EXCEPT WHEN REQUIRED INDIRECT WASTE
13) INSTALL A DIRECT CONNECTION AT 3 COMP SINK FOR WASH AND RINSE COMPARTMENTS
01/11/2012 SITE - SEWER BBENEDON Approved IVRS - Inspection :*
1) INTERCEPTOR AND SEWER OK TO COVER
02/27/2012 SHEET ROCK NAILING JMILITEL Approved IVRS - Inspection :*
04/25/2012 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
04/25/2012 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
04/25/2012 PLUMBING - GAS PRESSURE TEST JMILITEL Approved IVRS - Inspection :*
05/11/2012 PLUMBING - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
05/11/2012 PLUMBING - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
05/25/2012 ELECTRIC - UFER DWALKER Approved
05/25/2012 ELECTRIC - ABOVE CEILING DWALKER Approved
05/25/2012 ELECTRIC - FINAL DWALKER Approved IVRS - Inspection :*
07/26/2012 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
07/27/2012 FIRE - KITCHEN EXH HOOD FINAL WMOTTO Approved
07/30/2012 FIRE SPKLR - FINAL CBASALDU Approved
07/30/2012 FIRE - ALARM FINAL CSCHULTZ Approved
07/31/2012 FIRE - FINAL CBASALDU Approved
08/02/2012 PLUMBING - YARD WTR LINE/TEST BBENEDON Approved IVRS - Inspection :*
08/02/2012 PLUMBING - YARD WTR LINE/TEST BBENEDON Approved IVRS - Inspection :*
08/02/2012 PLUMBING - FINAL BBENEDON Approved IVRS - Inspection :*
08/02/2012 PLUMBING - PROGRESS BBENEDON Approved IVRS - Inspection :*
08/03/2012 BUILDING - FINAL DWALKER Approved IVRS - Inspection :*
08/03/2012 BUILDING - PROGRESS DWALKER Approved IVRS - Inspection :*
08/03/2012 BUILDING ABOVE CEILING DWALKER Approved IVRS - Inspection :*
08/07/2012 RIGHT OF WAY - FINAL P.Whiddon Approved
08/07/2012 NPPO - FINAL RLEDONNE Approved NA TO THIS ACTIVITY.
08/07/2012 SIGN - FINAL RLEDONNE Approved NA TO THIS ACTIVITY.
08/07/2012 LANDSCAPE - FINAL RLEDONNE Approved NA TO THIS ACTIVITY.
08/07/2012 ENGINEERING - FINAL RLEDONNE Approved NO CHANGE TO OUT SIDE OF BUILDING PER AP PLANS.

Documents

File Name Document Type  
001_T.1.TIF CONSTRPLANS VIEW
002_D.1.TIF CONSTRPLANS VIEW
003_A.1.TIF CONSTRPLANS VIEW
004_A.2.TIF CONSTRPLANS VIEW
005_A.3.TIF CONSTRPLANS VIEW
006_A.4.TIF CONSTRPLANS VIEW
007_A.5.TIF CONSTRPLANS VIEW
001_A-6.TIF CONSTRPLANS VIEW
008_E.1.TIF CONSTRPLANS VIEW
009_E.2.TIF CONSTRPLANS VIEW
010_E.3.TIF CONSTRPLANS VIEW
011_M.1.TIF CONSTRPLANS VIEW
012_M.2.TIF CONSTRPLANS VIEW
013_M.3.TIF CONSTRPLANS VIEW
014_P-1.TIF CONSTRPLANS VIEW
015_P-2.TIF CONSTRPLANS VIEW
016_P-2A.TIF CONSTRPLANS VIEW
017_P-3.TIF CONSTRPLANS VIEW
018_P-4.TIF CONSTRPLANS VIEW
001_A-1.1.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW