Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T11CM02865
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/25/2012 | ELECTRIC - UNDERGROUND | Approved | ||
12/27/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) INSTALL VDV CABLEING 725.8, 800.24 2) WIRING AT SPRINKLER VALVE IN WALL OK UNDERGROUND NOTE SOME RUNS HAVE 360 DEGREE (GROUND)-WILL NEED JUNCTION BOXES COMMING OUT OF WALLS OK WALL EXCEPT AS NOTED 3) 1200 AMP SES TO HAVE CLEARANCES PER 110.26(c) |
|
12/22/2011 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |