Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T11CM02865
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/11/2012 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/16/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PENDING REVISIONS FOR ALL CHANGES 2) RECALL PRIOR TO CEILING GRID AND PRIOR TO STTTING TOILETS FOR FLANGE INSPECTION |
|
02/15/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/07/2012 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* THANKS FOR THE LIGHTS 1. PLEASE MAKE YOUR ADDRESS VISIBLE 2. VENTS ABOVE CEILING REQUIRE A TEST 3. ALL PIPING ABOVE CEILING REQUIRE MORE SUPPORTS SEE UPC T-3 4. HAND SINKS REQUIRE 110 DEG. WATER NOT 140 DEG.; CORRECT 5. 2" CW SPECIFIED, PIPE 2" TO FIRST TEE 6. CHANGES TO PIPING LAYOUT AND SIZING REQUIRE A PLAN REVISION. 7. ALSO, PROVIDE A DETAIL OF FOUNTAIN WASTE RECEPTOR 8. PIPING INSULATION SPECIFIED FOR HW & CW. OK TO START 9. TEMP WATER BIB REQ VAC BREAKER 10. ARTURO CLAIMS ALL CU HAS BEEN REAMED 11. "3 COMP. SINK REQUIRES DIRECT CONN TO WASTE AS SHOWN ON PLAN" |
|
01/17/2012 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
01/03/2012 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |