Permit: T11CM02865

Parcel: 12212010A


Addresses:

4629 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T11CM02865

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
01/17/2012 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
01/11/2012 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
01/05/2012 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) AT LEAST 3 LOCATIONS WITH FLAT DRAIN PIPING
2) 3 LOCATIONS WITH UNDERSIZED PIPING AND CLEANOUTS
3) CORRECT SLOPE IN AL AREAS INCLUDING MS, GW, COMBO WASTE. CORRECT SIZING AND PROVIDE FULL SIZED CLEANOUTS
4) ALL PIPING SHALL BE SIZED AS SHOWN ON YOUR PLAN
5) PROVIDE MISSION COUPLINGS AT C1 TO P1 TRANSITION
6) FILL INTERCEPTOR TO TEST CONNECTIONS
7) 3 X 2 RESTRICTIONS CREATE A FOULING AREA AND AREA CODE VIOLATION, INSTALL PROPERLY SIZED FLOOR SINKS
8) TYPE K CU SPECIFIED BELOW SLAB
01/03/2012 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/28/2011 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE SAFE LIGHTING FOR INSPECTION
2) REMOVE ROCKS AND MUD
3) ALL PIPING REQUIRES CONTINOUS SUPPORT
4) SHADE PIPEING WITH CLEAN FILL
5) INSTALL PIPING PER PLAN AND PROVIDE DOCUMENTATION FOR ANY CHANGES-MANY SIZE DISCREPENCIES
6) COMBINATION WASTE AND VENT REQUIRES 2" FLOOR SINKS WITH A 2 X 3 INCREASER ON TAIL PIECE AS SHOWN ON YOUR PLAN
7) THE POINT OF VENT FOR ALL VENTS SHALL BE TAKEN OFF ABOVE THE CENTER LINE OF THE DRAIN SERVED (ROLL UP AT 45 DEGREE MINIMUM)
8) RE-VENTS SHALL BE 6" ABOVE THE FLOOD LEVEL OF THE HIGHEST FLANGE
9) CORRECT SLOPE
10) GW HAS BACK PITCH
11) ALL DRAIN LINES REQUIRE FULL SIZED CLEANOUTS
12) A DIRECT CONNECTION IS REQUIRED PER UPC 704.3 FOR ALL FIXTURES EXCEPT WHEN REQUIRED INDIRECT WASTE
13) INSTALL A DIRECT CONNECTION AT 3 COMP SINK FOR WASH AND RINSE COMPARTMENTS
12/22/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*