Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T11CM02865
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2012 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
01/11/2012 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
01/05/2012 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) AT LEAST 3 LOCATIONS WITH FLAT DRAIN PIPING 2) 3 LOCATIONS WITH UNDERSIZED PIPING AND CLEANOUTS 3) CORRECT SLOPE IN AL AREAS INCLUDING MS, GW, COMBO WASTE. CORRECT SIZING AND PROVIDE FULL SIZED CLEANOUTS 4) ALL PIPING SHALL BE SIZED AS SHOWN ON YOUR PLAN 5) PROVIDE MISSION COUPLINGS AT C1 TO P1 TRANSITION 6) FILL INTERCEPTOR TO TEST CONNECTIONS 7) 3 X 2 RESTRICTIONS CREATE A FOULING AREA AND AREA CODE VIOLATION, INSTALL PROPERLY SIZED FLOOR SINKS 8) TYPE K CU SPECIFIED BELOW SLAB |
|
01/03/2012 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
12/28/2011 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SAFE LIGHTING FOR INSPECTION 2) REMOVE ROCKS AND MUD 3) ALL PIPING REQUIRES CONTINOUS SUPPORT 4) SHADE PIPEING WITH CLEAN FILL 5) INSTALL PIPING PER PLAN AND PROVIDE DOCUMENTATION FOR ANY CHANGES-MANY SIZE DISCREPENCIES 6) COMBINATION WASTE AND VENT REQUIRES 2" FLOOR SINKS WITH A 2 X 3 INCREASER ON TAIL PIECE AS SHOWN ON YOUR PLAN 7) THE POINT OF VENT FOR ALL VENTS SHALL BE TAKEN OFF ABOVE THE CENTER LINE OF THE DRAIN SERVED (ROLL UP AT 45 DEGREE MINIMUM) 8) RE-VENTS SHALL BE 6" ABOVE THE FLOOD LEVEL OF THE HIGHEST FLANGE 9) CORRECT SLOPE 10) GW HAS BACK PITCH 11) ALL DRAIN LINES REQUIRE FULL SIZED CLEANOUTS 12) A DIRECT CONNECTION IS REQUIRED PER UPC 704.3 FOR ALL FIXTURES EXCEPT WHEN REQUIRED INDIRECT WASTE 13) INSTALL A DIRECT CONNECTION AT 3 COMP SINK FOR WASH AND RINSE COMPARTMENTS |
|
12/22/2011 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* |