Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T11CM02865
Parcel: 12212010A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02865
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/23/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Question: if waterless urinals are being specified, why are the ¾" branch pipes to the urinals still shown on sheet P-3? [Second comment: Comment not resolved; revise the branch piping to the urinals to limit the water velocity to 8 FPS.] [Original comment: Clarify the type of urinal that is to be installed. The plumbing fixture schedule on sheet p.1 calls out a waterless urinal but the drainage fixture units calculation on sheet P.1, the water fixture units calculation on sheet P-3, and the water riser diagram also located on sheet P-3 all indicate a urinal equipped with a 1-GPF flush valve. If the urinals do have flush valves, the ¾" branch piping sizes called out will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 103.2.3, 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.]
2. A Watts model SD-3 dual check valve is not acceptable to the City of Tucson for providing backflow protection for carbonated beverage dispensers; again, an ASSE 1013-rated backflow preventer is acceptable. [Second comment: Comment not resolved; a Watts model 909 is listed under ASSE 1013 (acceptable for carbonated beverage dispensers by the City of Tucson), a dual check valve with an intermediate atmospheric vent (ASSE 1012) is acceptable for most other appliances.] [Original comment: Appliances (e.g. ovens, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. The water riser diagram on sheet P-3 calls for vacuum breakers at each water connection; specify the type of vacuum breaker to be installed and any mounting requirements for the vacuum breakers. Soda dispensers require the use of a reduced backflow prevention assembly. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.]
11/23/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; the mechanical code compliance certificate only states that you have performed the required load calculations. Provide the load calculations. [Original comment: The current plans show an increase of 30-tons of air conditioning on an existing building; Provide calculations to show that the proposed increase complies with the requirements of Section 503.2, IECC 2006.]
11/28/2011 GERRY KOZIOL WWM REVIEW Denied NEED PCRWRD 3RD FLOOR CAPCITY EVALUATION - KURT STEMM- 740-6534
NEED TO SHOW EXSISTING LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER- NEED TO REVIEW SIZING OF EXSISTING PRIVATE SEWER - MAY NEED DEQ REVIEW & APPROVAL IF OVER 3000 GAL/DAY - DAVE AMISH243-7400- 33 N STONE AV
12/07/2011 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/13/2011 DELMA ROBEY OUT TO CUSTOMER Completed
12/13/2011 SUE REEVES REJECT SHELF Completed