Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Address NEW:
1650 W VALENCIA RD
Apply Date:
04/06/2010
Applicant:
N/A
Description:
TI: RETAIL (WALMART #1612 REVISION 1: VARIOUS CHANGES, SEE CCD 4 and 6 REVISION 4: VARIOUS CHANGES MOSTLY MECH
Contractors:
  • H B I CONSTRUCTION INCORPORATED (FN)

Permit Reviews

Permit Number - T10CM00905
Permit Status: Final
Permit Description: TI: RETAIL (WALMART #1612 REVISION 1: VARIOUS CHANGES, SEE CCD 4 and 6 REVISION 4: VARIOUS CHANGES MOSTLY MECH
Start Date Submittal Complete Date Status  
04/06/2010 PLANS OK TO SUBMIT - COMM 04/06/2010 COMPLETED Review Details
04/07/2010 COMMERCIAL TI 05/12/2010 COMPLETED Review Details
05/12/2010 OTHER 05/12/2010 COMPLETED Review Details
05/24/2010 RESUBMITTAL 06/08/2010 COMPLETED Review Details
06/08/2010 RESUBMITTAL 06/10/2010 COMPLETED Review Details
07/08/2010 REVISION - - 1ST 07/22/2010 COMPLETED Review Details
07/22/2010 REVISION - - 1ST 09/27/2010 COMPLETED Review Details
07/28/2010 REVISION - - 2ND 08/23/2010 COMPLETED Review Details
08/23/2010 REVISION - - 2ND 09/27/2010 COMPLETED Review Details
09/16/2010 REVISION - - 3RD 10/13/2010 COMPLETED Review Details
10/13/2010 REVISION - - 3RD 10/18/2010 COMPLETED Review Details
10/18/2010 REVISION - - 4TH 10/18/2010 COMPLETED Review Details
11/16/2010 REVISION - - 5TH 11/16/2010 COMPLETED Review Details

Completed Inspections

Permit Status: Final
Permit Number: T10CM00905
Permit Description: TI: RETAIL (WALMART #1612 REVISION 1: VARIOUS CHANGES, SEE CCD 4 and 6 REVISION 4: VARIOUS CHANGES MOSTLY MECH
Total Completed Inspections - 39
Date Description Inspector Results Comments
07/02/2010 ELECTRIC - UNDERGROUND RMORENO Approved IVRS - Inspection :*
1) FLOOR BOX TO FLOOR BOX 3/4 PVC TO SOUTH WAL FOR FREEZERS ALL OK
2) RECEIVED $150.00 FROM CONTRACTOR FOR AFTER HOURS INSPECTION
12/03/2010 BUILDING ABOVE CEILING MHENSON Approved IVRS - Inspection :*
1) JUICE AREA CLIPS IN PLACE
2) NO TILES INSTALLED UNTIL ALL TRADES OK
12/06/2010 MECHANICAL - ABOVE CEILING MRAMBER Approved IVRS - Inspection :*
1) 36" DUCT ABOVE PRODUCE PREP OK TO COVER
12/07/2010 PLUMBING - GAS PRESSURE TEST RLEDONNE Approved IVRS - Inspection :*
1) 60 PSI TEST OK
12/08/2010 FIRE SPKLR - FINAL LTHOMAS Approved Hds missing on line
2 hds in exit corr.
plywood off
1 painted head
1 hd in dinning closet
12/09/2010 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :*
1) WALL PLUG FOR WATER DISPENSOR IS BEING DELETED
2) HEAT TABLES INSTALLED PER MANUFACTURERS INSTRUCTIONS
3) OK ABOVE CEILING BAKERY/HOT DELI
4) FINISH MAIN BREAKER AND ENCLOSE CHANGE OUT FOR "L4D3"
12/09/2010 PLUMBING - GAS PRESS TEST FNL RLEDONNE Approved IVRS - Inspection :*
1) UNCOVER ALL AAVS
2) PROVIDE ALL BACKFLOW CERTS
3) COMPLETE ALL SUPPORT ON WATER AND DRAIN PIPING
4) COMPLETE ALL MIXING STATION AT SINKS AND MOP SINKS
5) GAS OK IN BAKERY AREA
12/10/2010 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*
1) CANCELLED
12/10/2010 BUILDING - PROGRESS MHENSON Approved IVRS - Inspection :*
1) JUICE BAR OK TO OCCUPY
2) FOR FINAL TRADES, FIRE AND ENGINEERING FINALED
3) SPECIAL INSPECTION CERT DBL STAMPED
12/13/2010 FIRE - KITCHEN EXH HOOD FINAL DRAMIREZ Approved
12/13/2010 MECHANICAL - FINAL MRAMBER Approved
12/13/2010 BUILDING PRE-SLAB MHENSON Approved IVRS - Inspection :*
12/13/2010 STEM WALL/RETAINING WALL MHENSON Approved IVRS - Inspection :*
12/13/2010 EXCAVATION/LAYOUT REBAR & ZON MHENSON Approved IVRS - Inspection :*
12/13/2010 MECHANICAL - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
12/13/2010 NPPO - FINAL DROBERTS Approved
12/13/2010 LANDSCAPE - FINAL DROBERTS Approved
12/14/2010 ELECTRIC - PROGRESS RHOLLAND Approved IVRS - Inspection :*
BAKERY:
1) VERIFY INSTRUCTIONS FOR FREEZER DOOR
2) NEED WATER HEATER INSTALLED
3) FIX DOOR HARDWARE PANELS L4D3-SEC 1, 2 AND 3
4) RECEIVED MONEY ORDER FOR $165.00
12/14/2010 PLUMBING - FINAL RLEDONNE Approved IVRS - Inspection :*
12/16/2010 BUILDING - FINAL MHENSON Approved IVRS - Inspection :*
1) FIRE CAULKING OUT EXIT CORRIDORS NEED TO BE CHECKED
12/16/2010 SHEET ROCK NAILING MHENSON Approved IVRS - Inspection :*
12/16/2010 FRAMING MHENSON Approved IVRS - Inspection :*
12/16/2010 REINFORCED MASONRY PRE-GROUT MHENSON Approved IVRS - Inspection :*
10/20/2011 MECHANICAL - PROGRESS MRAMBER Approved IVRS - Inspection :*
11/10/2011 RIGHT OF WAY - FINAL MCASTRO Approved
12/15/2011 FIRE - FINAL WMOTTO Approved
12/16/2011 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
1) MET WITH JOHN WENT OVER ITEM TO BE DONE
2) REVIEW AND REPAIR
12/20/2011 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
12/20/2011 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
12/20/2011 PLUMBING - PRE SLAB RMYERS Approved IVRS - Inspection :*
12/20/2011 PLUMBING - PROGRESS RMYERS Approved IVRS - Inspection :*
12/20/2011 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*
12/21/2011 MECHANICAL - HOODS MRAMBER Approved IVRS - Inspection :*
12/21/2011 MECHANICAL - UNDERGROUND MRAMBER Approved IVRS - Inspection :*
12/22/2011 SIGN - FINAL RLEDONNE Approved NA TO THIS ACTIVITY.
12/22/2011 ENGINEERING - FINAL RLEDONNE Approved TALK WITH JOHN TO COMPLET AP PLANS FOR ENGNEERING FINAL.
01/19/2012 FIRE - ALARM FINAL CSCHULTZ Approved No alarm work done
01/23/2012 ELECTRIC - UFER RHOLLAND Approved IVRS - Inspection :*
03/05/2012 HEALTH DEPT - FINAL 724-7908 AKincaid Approved